19
7704679.01 (3-08/18)
B) FLOW TEMPERATURE MODULATION
To set flow temperature modulation, disable parameter
742
(HC1). Proceed as follows:
•
Access menu
2
.
•
B
Temps / mode CH1
B
to confirm
B
742
(Flow temp setpoint room stat)
B
to confirm.
•
B
(anti-clockwise)
"
---
" then
B
to confirm.
If, when turning the knob
B
on the main menu, the display visualises the boiler flow temperature instead of the ambient
temperature, parameter
742
has not been set correctly.
After every system configuration (e.g.: solar combination, connection an external storage boiler, etc.) perform the following
procedure to update the boiler board to the new configuration:
•
Access menu 2 as indicated at the beginning of this section.
•
B
Configuration
B
B
programme row
6200
then
B.
•
B
Yes
then
B
to confirm.
ZONE SYSTEM WITH INSTALLATION OF THE REMOTE CONTROL
The electrical connection and the adjustments required to manage a system divided into zones with use of the Remote Control
differs according on the accessories connected to the boiler. To install and configure, see the instructions of the
Expansion
Module
supplied as an accessory.
ADJUSTING THE TEMPERATURE OF THE HIGH TEMPERATURE HEATING SYSTEM
To avoid frequent starting and stopping, raise the minimum temperature setpoint of the boiler in the heating mode by setting
parameters
740
, to not less than 25°C, using the procedure described in point
B
.
TEMPERATURE ADJUSTMENT ON
LOW TEMPERATURE HEATING SYSTEM
For a low temperature system (such as underfloor heating), reduce the maximum CH temperature setpoint on the boiler by setting
parameter
741
(point B
)
to a value not greater than 55°C.
8.2 OUTDOOR SENSOR
The External Probe can be connected to the boiler as
illustrated in the figure to the side. The following procedure is
used to set a parameter, called
room influence
which is used
to determine the importance of the ambient temperature with
respect to the external temperature and vice-versa (the factory
setting is 50%-50%).
E.g.
: if the ambient influence is set to 60%, the influence of
the External Probe will consequently be 40% (the greater the
set value of ambient influence, the lesser the influence of the
External Probe will be in proportion, and vice-versa).
The following procedure is used to set ambient influence:
•
C
then
A
and
C
(approx. 6 seconds)
Enduser – Commissioning - Engineer - OEM.
•
B
"
Commissioning
"
B
to confirm.
•
B
"
Temps / mode CH1
"
B
to confirm.
•
B
programme row
750
(Room influence)
B
to confirm.
•
B
and choose the
%
value to assign to the parameter that determines how much the ambient affects the system then
B
to confirm.
•
C
to return to the previous menu.
SETTING THE "Kt" CLIMATE CURVE
To set the climate curve
Kt,
access
menu 2
as described in section 8.1.1 and proceed as follows:
•
B
720
(Heating curve slope)
B
to confirm
•
B
(
from 0.10 to 4
)
B
to confirm.
•
Select the climate curve from among those available, see the curve chart in chap.
"OUTDOOR SENSOR"
(the preset curve
is 1.5).
KEY TO CURVE CHART Kt - see chap.
"OUTDOOR SENSOR"
Flow temp
Outside temp
Summary of Contents for Sirius Three WH-130
Page 1: ...May 2018 Sirius three WH 130 150 kW ...
Page 10: ...7704679 01 3 08 18 10 583 892 600 G 1 1 2 G 1 1 2 G 1 198 100 100 100 102 CR_0775 95 223 24 ...
Page 20: ...7704679 01 3 08 18 20 WEATHER COMPENSATION CURVE GRAPHS QAC34 ...
Page 35: ...35 7704679 01 3 08 18 29 DIAGRAMS AGU 2 550 CR_0349 CR_0349 AVS 75 bis ...
Page 36: ...7704679 01 3 08 18 36 CG_2482 SAFETY THERMOSTAT Tmax 50 C free contact ...
Page 37: ...37 7704679 01 3 08 18 MODIFIED PARAMETERS Nr VALUE NOTE ...
Page 38: ...7704679 01 3 08 18 38 ...
Page 39: ...39 7704679 01 3 08 18 ...