7704679.01 (3-08/18)
28
ENERGY-SAVING TIPS
Adjustment in the heating mode
Adjust the boiler flow temperature depending on the kind of system. For systems with radiators, set a maximum heating water
flow temperature of approximately 60°C, and increase this value if the required room temperature is not reached. For systems
with radiant floor panels, do not exceed the temperature indicated by the system designer. Use the External Sensor and/or
Control Panel to automatically adjust the flow temperature to atmospheric conditions or the indoor temperature. This ensures that
no more heat than that effectively necessary is produced. Use room thermostats to adjust the temperature without overheating
the rooms. Every extra degree centigrade means consuming approximately 6% more energy. Also room ambient temperature
depending on how the rooms are used. For example, the bedroom or the least used rooms can be heated to a lower temperature.
Use the programmable timer and set the night-time room temperature at approximately 5°C lower than that during the day. There
is no appreciable saving to be achieved by setting it any lower. Only in case of a prolonged absence, such as a holiday, should
the temperature setpoint be lowered. Do not cover radiators as this prevents the air from circulating correctly. Do not leave the
windows partially open to ventilate the rooms but open them completely for a short period.
Domestic hot water
Setting the domestic hot water at the required temperature without mixing it with cold water saves a lot of money. Additional heating
wastes energy and creates additional scale. Recommended minimum storage temperature of 60°C to reduce the Legionella risk.
20. ACCESS TO THE PARAMETER CONFIGURATION MENUS
KEY TO DISPLAY (see figure to side)
a
Date: day, month, year
b
Day of the week
c
Pressure in boiler / heating circuit
d
Clock: hour and minutes
To access the list of configuration menus, proceed as follows (consult the
"Description of Symbols" section):
C
B
to select the required menu;
B
to confirm or
C
to
exit without saving.
The list of configuration menus is:
•
Information (INFORMATION MENU)
•
Set time and date (TIME AND DATE MENU)
•
Operator unit (CHANGE LANGUAGE)
•
Time central heating (HOURLY PROGRAMMING)
•
Time central heating CH3
•
Time hot water
•
Time auxiliary
•
Holiday heating (HOLIDAY PROGRAMME)
•
Temps / mode
•
Temps / mode hot water
•
Instantaneous HW heater (not used)
•
Error (FAULTS)
• Diagnostics heat generation
20.1 INFORMATION MENU
In case a fault arises, the first data displayed is the fault code.
To display boiler information, select "
Information
" as indicated in section 20.
Boiler temperature
°C
Boiler flow temperature
Outside temp
°C
Outside temp
Outside temp min
°C
Minimum memorised outside temperature value (with external probe connected)
Outside temp max
°C
Maximum memorised outside temperature value (with external probe connected)
DHW temperature
°C
DHW temperature (value read by the boiler DHW circuit probe)
Manifold temperature
°C
Instantaneous temperature of manifold sensor (with connection to solar plant)
State central heating (1,2,3)
(On/Off)
Heating circuit operating mode (circuits: 1,2,3)
State hot water
Charging
DHW circuit operating mode
State boiler
(On/Off)
Boiler operating mode
Solar state
-
Indicates if sunlight is sufficient (with connection to solar plant)
Telephone customer service
n
xxxxxxxxxx
20.2 TIME AND DATE MENU
To set the time and date, follow the procedure indicated in section 20 and proceed as follows:
•
Access the
Set time and date menu
B
1 (Hours / minutes)
B
(the hour flashes)
•
B
to edit the hour
B
to confirm (the minutes flash)
B
to edit
B
to confirm.
•
B
to edit 2 (Day / month) and 3 (Year) performing the same procedure as above.
•
C
to return to the previous menu.
Summary of Contents for Sirius Three WH-130
Page 1: ...May 2018 Sirius three WH 130 150 kW ...
Page 10: ...7704679 01 3 08 18 10 583 892 600 G 1 1 2 G 1 1 2 G 1 198 100 100 100 102 CR_0775 95 223 24 ...
Page 20: ...7704679 01 3 08 18 20 WEATHER COMPENSATION CURVE GRAPHS QAC34 ...
Page 35: ...35 7704679 01 3 08 18 29 DIAGRAMS AGU 2 550 CR_0349 CR_0349 AVS 75 bis ...
Page 36: ...7704679 01 3 08 18 36 CG_2482 SAFETY THERMOSTAT Tmax 50 C free contact ...
Page 37: ...37 7704679 01 3 08 18 MODIFIED PARAMETERS Nr VALUE NOTE ...
Page 38: ...7704679 01 3 08 18 38 ...
Page 39: ...39 7704679 01 3 08 18 ...