24. ADJUSTMENT AND SAFETY DEVICES
The boiler has been designed in full compliance with European reference standards and in particular is equipped with the following:
•
Limit thermostat
Thanks to a sensor placed on the CH flow line, this thermostat interrupts the flow of gas to the burner if the water in the primary
circuit overheats.
•
Exchanger flange thermostat (260°C)
This device is located on the exchanger flange and interrupts the flow of gas to the burner if the front insulation yields and
overheats the exchanger or the flange gasket develops a fault. Press the reset button on the thermostat and eliminate the fault.
•
Thermal fuse
This device is located at the rear of the exchanger and interrupts the flow of gas to the burner if the rear insulation yields and
overheats the exchanger. If this device cuts in, dismount the exchanger and replace the thermal fuse (see paragraph “THERMAL
FUSE REPLACEMENT OF HEAT EXCHANGER”).
It is forbidden to disable this safety device.
•
NTC flue sensor
This device is positioned on the fumes duct. The electronic board stops gas from flowing to the burner in case of over heating.
The above reset operation is only possible if the temperature is less than 90°C.
It is forbidden to disable this safety device
•
Fumes pressure switch
This device stops the flow of gas to the burner when the pressure in the flue ducts exceeds 600 Pa. Under these conditions, the
boiler is blocked and only after the fault has been eliminated can the boiler be ignited again (see section “FAULTS THAT CANNOT
BE RESET BY THE USER”).
•
Flame ionisation detector
The flame sensing electrode guarantees safety of operation in case of gas failure or incomplete ignition of the main burner. In
these conditions, the boiler blocks.
•
Hydraulic pressure switch
This device allows the main burner to be ignited only if system pressure is higher than 1 bar.
•
Pump post-circulation
The electronically-controlled pump post-circulation function lasts 3 minutes and is enabled, in the heating mode, if the ambient
thermostat causes the main burner to go out.
•
Antifreeze device
The electronic boiler management system includes an "antifreeze" function for the heating and DHW systems which, when flow
temperature falls below 5°C, operates the burner until a flow temperature of 30°C is reached. This function is enabled when the
boiler is switched on, the gas supply is open and the system is correctly pressurised.
•
Pump anti-block function
If no heat demand is received in the heating and/or DHW modes for 24 consecutive hours, the pumps will automatically start and
operate for 10 seconds.
•
Hydraulic safety valve (heating circuit)
This device is set to 6 bar and is used for the heating circuit. Connect the safety valve to a drain trap. Do not use it to drain the
heating circuit.
•
Heating pump pre-circulation
In case of a heat demand in the heating mode, the appliance can pre-circulate the pump before the burner is ignited. This pre-
circulation phase last from a few seconds to a few minutes, depending on the operating temperature and installation conditions.
•
Gas pressure switch
This device enables the main burner only to be switched on if the gas pressure is over 12 mbar.
The functions performed by the adjustment and safety devices are only operative if the boiler is switched on.
25. ROUTINE MAINTENANCE INSTRUCTIONS
To keep the boiler efficient and safe, have it checked by a competent person at the end of every 12 months.
Careful servicing ensures economical and safe operation of the system.
Summary of Contents for Sirius Three WH-130
Page 1: ...May 2018 Sirius three WH 130 150 kW ...
Page 10: ...7704679 01 3 08 18 10 583 892 600 G 1 1 2 G 1 1 2 G 1 198 100 100 100 102 CR_0775 95 223 24 ...
Page 20: ...7704679 01 3 08 18 20 WEATHER COMPENSATION CURVE GRAPHS QAC34 ...
Page 35: ...35 7704679 01 3 08 18 29 DIAGRAMS AGU 2 550 CR_0349 CR_0349 AVS 75 bis ...
Page 36: ...7704679 01 3 08 18 36 CG_2482 SAFETY THERMOSTAT Tmax 50 C free contact ...
Page 37: ...37 7704679 01 3 08 18 MODIFIED PARAMETERS Nr VALUE NOTE ...
Page 38: ...7704679 01 3 08 18 38 ...
Page 39: ...39 7704679 01 3 08 18 ...