3. Open the front panel.
4. Check the gas supply pressure at the pressure outlet on the gas valve
unit.
5. Check the tightness of the gas connections made after the gas valve
unit in the boiler.
6. Check the tightness of the gas pipe, including any valves, from the
non-return valve to the burner. The test pressure must not exceed
0.06 bar (0.006 MPa).
7. Vent the gas supply pipe by unscrewing the pressure outlet on the gas
valve unit. Close the outlet again when the pipe has been sufficiently
vented.
8. Check the tightness of the gas connections in the boiler.
For more information, see
7.3.3
Checking the electrical connections
1. Check for the presence of the recommended circuit breaker.
2. Check the electrical connection to the mains.
3. Check the connection of the sensors.
4. Check the position of the sensors. Respect the distance of the
sensors according to the power.
5. Check the connection of the circulating pump(s).
6. Check the connection of the optional equipment.
7. Check the length of the cables and that they are firmly secured in the
cable clamps.
7.3.4
Checking the hydraulic circuit
1. Check the siphon, which must be completely filled with water.
2. Check that there are no leaks on the boiler's hydraulic connections.
3. Check the pressure in the expansion vessel before filling the system.
7.4
Gas settings
7.4.1
Configuring the fan speed
The boiler's fan speed has to be configured according to gas type before
the gas valve is set.
1. Go to the installer parameters.
2. Select the Boiler Settings menu by turning the
button.
3. Confirm the menu selection by pressing the button .
4. Modify parameter 2441 Fan speed heating max according to the gas
type. Use the button to select and modify the parameter.
5. Confirm the setting by pressing the button.
6. Select the Burner control menu by turning the
button.
7. Modify parameters 9512 Required speed ignition, 9524 Required
speed LF and 9529 Required speed HF according to the gas type.
Use the button to select and modify the parameters.
For more information, see
Modifying the installer parameters, page 68
7 Commissioning
7609493 - v08 - 24072018
57