11 Troubleshooting
11.1 Error codes
A Error code
B Secondary error code
C Description of the error
Important
Press the
MENU
key to return to the main display.
The
symbol continues to be displayed on the control panel.
If the error is not resolved after one minute, the error code is
displayed on the control panel a second time.
Tab.74 List of error codes
Display
Description of the error
20
20:Boiler sensor 1
Flow back sensor.
28
28:Flue gas temp sensor
Flue gas sensor.
40
40:Return sensor 1
Return temperature sensor.
46
46:Return sensor cascade
Cascade return temperature sensor error.
52
52:HW sensor 2
Solar domestic hot water sensor (if incorporating a solar sys
tem).
60
60:Room sensor 1
Room temperature sensor 1 error.
65
65:Room sensor 2
Room temperature sensor 2 error.
68
68:Room sensor 3
Room temperature sensor 3 error.
78
78:Water pressure sensor
Hydraulic pressure sensor error.
73
73:Collector sensor 1
Solar collector sensor (if incorporating a solar system).
83
83:BSB short-circuit
Communication problem between boiler PCB and control
unit. Probable short circuit on the heating.
84
84:BSB address collision
Address conflict between several control units (internal
anomaly).
91
91:Data loss in EEPROM
Loss of data in EEPROM.
98
98:Extension module 1
Extension module 1 error.
99
99:Extension module 2
Extension module 2 error.
100
100:2 clock time masters
2 master clocks
102
102:Clock without backup
Master clock with no power reserve.
103
103:Communication failure
Communication error.
109
109:Boiler temp supervision
Air present in the boiler circuit (anomaly)
117
117:Water pressure too high
Pressure in hydraulic circuit too high.
118
118:Water pressure too low
Pressure in hydraulic circuit too low.
125
125:Boiler temp too high
Safety cut-off for absence of circulation (check made by a
sensor).
128
128:Loss of flame in op
Flame extinguished.
130
130:Flue gas temp too high
Cut-off by flue gas sensor for overheating.
151
151:BMU internal
Internal error on heating PCB.
152
152:Parameterization
General parameter setting error.
153
153:Unit locked
Appliance locked manually.
160
160:Fan speed threshold
Fan operation error.
171
171:Alarm contact 1 active
ACI board error.
178
178:Limit thermostat CH1
Safety thermostat CH1.
179
179:Limit thermostat CH2
Safety thermostat CH2.
321
321:HW outlet sensor
Domestic hot water sensor damaged.
Fig.132 Error code
Error
118: Water pressure too low
0,4 bar
BM-0000026-GB-03
A
B
C
11 Troubleshooting
112