Display
Description of the error
343
343:Solar integration missing
General parameter setting error on the solar system (if incor
porating a solar system).
353
353:Casc sens B10 missing
B10 cascade sensor missing.
372
372:Limit thermostat CH3
Safety thermostat CH3.
373
373:Extension module 3
Extension module 3.
384
384:Extraneous ligth
Light incorrect (parasite flame — internal anomaly).
385
385:Mains undervoltage
Power supply voltage too low.
386
386:Fan speed tolerance
Fan threshold speed not reached.
430
430:Dyn water pres too low
Safety cut-off for absence of circulation (check made by a
pressure sensor).
432
432:Function ground missing
Earthing function not connected.
Important
This list is not exhaustive. Other error codes may be displayed.
Contact the accredited technical assistance service.
Important
If the display of the error code persists, contact the accredited
assistance service.
Important
If the error code simultaneously displays the and symbols,
contact the accredited technical assistance service.
For more information, see
Cleaning the heat exchanger, page 103
Standard inspection and maintenance operations, page 100
Remounting the burner, page 105
Thermal fuse in the heat exchanger, page 106
Check the combustion, page 107
Checking combustion (maximum heat input), page 107
Checking combustion (reduced heat input), page 109
11.1.1 Automatic error code clearing
If the symbol is displayed at the same time as the error code, the error
code is automatically cleared when the cause that prompted it stops.
A flow or return temperature in excess of the critical value prompts an
error code. The error code is automatically cleared when the temperature
drops below the critical value.
For more information, see
Cleaning the heat exchanger, page 103
Standard inspection and maintenance operations, page 100
Remounting the burner, page 105
Thermal fuse in the heat exchanger, page 106
Check the combustion, page 107
Checking combustion (maximum heat input), page 107
Checking combustion (reduced heat input), page 109
11.1.2 Clearing error codes
If the probable cause of an error code is resolved but the error code
continues to be displayed, proceed as follows to clear the error code:
1. Press the button.
The command Reset? Yes is displayed on the control panel.
11 Troubleshooting
7609493 - v08 - 24072018