Potterton Solar - Solar Thermal Domestic Hot Water System
13
3.0
Commissioning of solar controller
3.1.6 Menu “Programming”
All adjustable parameters can be checked in this menu
and, if necessary, changed.The default factory set values
will usually give efficient, problem free operation.
The number of indicated values depends on the
controller type and the adjusted additional functions.
Only the required values are shown at each menu step:
Indication
Description
Value range
Defaults
max
Storage 1/2:
15..95ºC
65ºC
65ºC
Maximum temperature
dT max
Storage 1/2: Hysteresis (Tdon)
3..40 K
7 K
7 K
dT min
Storage 1/2: Hysteresis (Tdoff)
2..35 K
3 K
3 K
min
Setting the speed control of the pump
30%..100%
100%
100
100% = speed control off
13:21
Clock
0:00...23.59
12:00
min
Temperature start for the function
20..90ºC
40ºC
40ºC
heating/cooling
dT
Hysteresis heating/cooling
1..30K
10K
10K
max
Differential controller: Maximum
15..95ºC
65ºC
65ºC
temperature of heat target Tmax
min
Differential controller: Maximum
0..95ºC
15ºC
15ºC
temperature of heat source Tmin
dTmax
Temperature differential controller:
3..40K
7K
7 K
Hysteresis dTmax
dT min
Temperature differential controller:
2..35K
3K
3 K
Hysteresis dTmin
min
Timeframe 1(2,3): Start
0:00...
00:00
00:00
for the independent controller
23.59
1(2,3)
max
Timeframe 1(2,3): Stop
0:00...
23:59
23:59
for the independent controller
23:59
1(2,3)
min
Timeframe 1(2,3): Start
0:00...
6:00
6:00
for the tube collector function
23:59
4
max
Timeframe 1(2,3): Stop
0:00...
20:00
20:00
for the tube collector function
23:59
4
2