Potterton Solar - Solar Thermal Domestic Hot Water System
26
Resistance table PT1000.
The correct function of temperature sensors can be
checked on the basis of the following temperature
resistance table with a resistance measuring instrument:
5.0
Fault finding
Temperature in ºC
Resistance in Ohm
-30
882
-20
921
-10
960
0
1000
10
1039
20
1077
30
1116
40
1155
50
1194
60
1232
70
1271
80
1309
90
1347
100
1385
120
1461
140
1535
200
1758
YES
No display at solar differential
temperature controller
Controller fault
Replace controller
Is the 230/240V~ power
supply switched on
YES
Has thermal cutout
on cylinder operated
(unvented systems only)
NO
NO
Is internal
fuse operational
YES
NO
Replace internal fuse
Check wiring and rectify
Reset thermal cutout.
Investigate cause of operation
and rectify
Is the 230/240V~
power supply at the controller
terminal block
Switch on power supply
Is the 230/240V~ power
supply correctly wired
YES
NO
YES
NO
Correct any wiring faults