Powered by Safety
®
32
Installation
PowlVac® ARG & ARM Series 4 Vacuum Circuit Breakers
5kV & 15kV - 1200A, 2000A, & 3000A - 25kA, 36kA, 50kA, & 63kA
01.4IB.60306
1) Prior to Inserting the Circuit Breaker into the
Circuit Breaker Compartment
a. Check the Primary Disconnecting
Devices and Circuit Breaker
Compartment
Examine the primary disconnecting
devices for any signs of damage and
contamination. Check to see that
none are bent out of alignment. If
contamination is found refer to
Description, 2) Inspection and Cleaning
Ch 5 Maintenance, B. Mechanism
for cleaning and
lubrication procedures. If the primary
disconnecting devices are damaged
make no attempt to repair. Contact
Powell for further information.
Examine the circuit breaker
compartment to see that it is clean and
clear of debris that might interfere with
circuit breaker travel.
Before inserting any circuit breaker into a
compartment, the user must verify that the
circuit breaker rating meets or exceeds the
metal-clad switchgear rating.
CAUTION
Before inserting a circuit breaker into
the circuit breaker compartment, be
sure that the indicator flag on the front
cover of the circuit breaker displays
“BREAKER TEST/DISCONNECTED”.
CAUTION
The illustrations shown for all racking
procedures are provided to show device
locations and are intended only as a guideline.
These illustrations may not be representative
of site specific safety practices for performing
the procedure. Before attempting any racking
procedure, review
.
NOTICE