01.4IB.51809
Powered by Safety
®
9
Installation & Operation
2. Equipment designed for outdoor exposure
may be stored either in indoor or outdoor
storage locations. The equipment must
be protected from airborne external
contaminates if stored outdoors. Outdoor
storage will also require additional care
to maintain temporary covers over
the openings and shipping splits. The
equipment must be provided with control
power to facilitate the energization of
space heaters, as well as other temperature
and humidity controlling equipment. The
temperature should be kept above freezing
(>33°F/1°C) and below (<140°F/60°C). The
relative humidity should be kept below
60% or a dew point of 15°C/59°F. The
equipment should be stored in such a
manner as to leave all doors and panels
accessible for inspection. The equipment
must be inspected on a routine basis to
assure its integrity.
3. The auxiliary control devices, ship loose
material and protective relays must also
be protected. This includes items such as
battery chargers, UPS systems, lighting,
installation hardware and air conditioning.
If prolonged storage is anticipated,
humidity controlling desiccant materials
should be utilized. Desiccant packets
should be installed in all compartments and
packing containers.
d. o
perAtIon
Do NOT work on an energized circuit breaker.
Follow circuit breaker safety guidelines and
operating instruction provided in the specific
circuit breaker instruction bulletin.
!
WARNING
Attaching and operating the electric racking
device can be accomplished by one person.
When circuit breaker racking is required, the
electric racking device engages the racking
handle of the breaker. The racking device is
operated by the motor control box.
When racking in a circuit breaker, move the
circuit breaker to the required switchgear
location.
For more information on the circuit breaker
handling, see the instruction bulletin for the
circuit breaker in use.