Ch 2 Safety
A. S
Afe
W
ork
c
ondItIon
The information in Section A is quoted from
NFPA 70E 2012 - Article 120, 120.1 Establishing an
Electrically Safe Work Condition.
120.1 Process of Achieving an Electrically Safe
Work Condition
1. Determine all possible sources of electrical
supply to the specific equipment. Check
applicable up-to-date drawings, diagrams,
and identification tags.
2. After properly interrupting the load current,
OPEN the disconnecting device(s) for each
source.
3. Wherever possible, visually verify that all
blades of the disconnecting devices are
fully OPEN or that drawout type circuit
breakers are withdrawn to the fully
disconnected position.
4. Apply lockout/tagout devices in accordance
with a documented and established policy.
5. Use an adequately rated voltage detector
to test each phase conductor or circuit part
to verify they are deenergized. Test each
phase conductor or circuit part both
phase-to-phase, and phase-to-ground.
Before and after each test, determine
that the voltage detector is operating
satisfactorily.
Informational Note:
See ANSI/ISA-
61010-1 (82.02.01)/UL 61010-1, Safety
Requirements for Electrical Equipment for
Measurement, Control, and Laboratory
Use - Part 1: General Requirements,
for rating and design requirements for
voltage measurement and test instruments
intended for use on electrical systems
1000V and below.
6. Where the possibility of induced voltages
or stored electrical energy exists, ground
the phase conductors or circuit parts
before touching them. Where it could be
reasonably anticipated that the conductors
or circuit parts being deenergized
could contact other exposed energized
conductors or circuit parts, apply ground
connecting devices rated for the available
fault duty.
B. S
Afety
G
uIdelIneS
Study this instruction bulletin and all other
associated documentation before uncrating
the controllers.
Each user has the responsibility to instruct
and supervise all personnel associated with
usage, installation, operation, and maintenance
of this equipment on all safety procedures.
Furthermore, each user has the responsibility of
establishing a safety program for each type of
equipment encountered.
The
medium voltage equipment described in
this instruction bulletin is operated by a
high-energy, high-speed mechanism that
is interlocked to provide specific operating
sequences. It is mandatory that the following
rules be observed to ensure the safety of
personnel associated with usage, installation,
operation, and maintenance of these
controllers.
The safety rules in this instruction bulletin are
not intended to be a complete safety program.
The rules are intended to cover only some of the
important aspects of personnel safety related to
Circuit Breaker Monitor (CBM).
Summary of Contents for AP.CBM.01 EIM
Page 1: ...Instruction Bulletin 01 4IB 48070A Circuit Breaker Monitor CBM Powered by Safety ...
Page 4: ...Powered by Safety Circuit Breaker Monitor 01 4IB 48070A This page is intentionally left blank ...
Page 13: ...5 Safety Powered by Safety 01 4IB 48070A This page is intentionally left blank ...
Page 29: ...Powered by Safety 21 Usage 01 4IB 48070A Figure 21 IRIM Production Assistant Screen ...