Powered by Safety
®
58
Operation
Power/Vac
®
Metal-Clad Switchgear 5kV & 15kV
01.4IB.67000
By maintaining a slight temperature
differential, the heaters help facilitate drying
and prevent condensation and the resulting
corrosion and insulation deterioration which
might occur.
Four 75-watt heaters are provided in each
vertical section. One heater is located in each
breaker or auxiliary compartment on the
bottom at the rear. One heater is also located
at the bottom of each cable compartment
when breakers are stacked two high. When
there is only one breaker per section both
heaters are located in the cable compartment
at the bottom of the section. Heaters may also
be located in transition compartments and in
bus ducts if the operating conditions require
them.
Before energizing the heaters, be sure the
power source is of the proper voltage,
frequency, and is connected in accordance
withe the wiring diagrams furnished with the
switchgear. Also, be sure to remove all cartons
and miscellaneous material packed inside the
units before energizing the heaters.
The heater circuit should be inspected several
times a year to make sure that it is energized.