Recommended Renewal Parts and Replacement Procedures
PowlVac® DHP 15kV Replacement Circuit Breaker
01.4IB.50032C
Ch 6 Recommended Renewal Parts and
Replacement Procedures
A. o
rDerInG
I
nStructIonS
1. Order Renewal Parts from Powell at
www.powellind.com or call 1.800.480.7273.
2. Always specify complete nameplate
information, including:
• Circuit Breaker Type
• Serial Number
• Rated Voltage
• Rated Amps
• Impulse Withstand
• Control Voltage (for control devices and
coils)
3. Specify the quantity and description
of the part and the instruction bulletin
number. If the part is in any of the
recommended renewal parts tables, specify
the catalog number. If the part is not in
any of the tables, a description should be
accompanied by a marked illustration from
this instruction bulletin, a photo or simply
submit a sketch showing the part needed.
B. r
ecoMMenDeD
r
eneWAl
p
ArtS
This section includes instructions for replacing
the parts recommended as renewal parts.
Before attempting any maintenance repair
work, take note of the safety practices outlined
in
of this instruction bulletin.
!
CAUTION
Ensure that the control circuits are
deenergized and the circuit breaker is
deenergized, disconnected by means of a
visible break, and securely grounded. Do NOT
start to work on a closed circuit breaker or
acircuit breaker with the main closing spring
charged. When any maintenance procedure
requires the opening or closing of the circuit
breaker or the charging of any of the stored
energy mechanism springs, exercise extreme
caution to ensure that all personnel, tools,
and other miscellaneous objects are kept
clear of the moving parts of the charged
springs.
1) Vacuum Interrupter Assembly
!
CAUTION
The vacuum interrupter should only be
replaced by a qualified person or a Powell
Service technician. Contact Powell for further
assistance at 1.800.480.7273.
!
CAUTION
Ensure all operating springs are discharged
and the circuit breaker is in the open position.
Failure to do so may result in personal injury
and/or damage to circuit breaker.
This assembly is located between the upper
and lower primary disconnecting devices
a. Remove the front cover of the circuit
breaker.
b. Remove the interphase barrier
assembly.