Powered by Safety
®
7
Equipment Description
01.4IB.51000C
B. D
ImenSIonS
The PowlVac® switchgear basic vertical sections
are available in two configurations:
1) One-high Construction
The basic one-high construction standard
measurements are 92” height x 36” width x
83-5/8” depth. The compartment holds one
circuit breaker. For special use, a one-high
construction with extended height, front,
center, and rear sections is available.
Figure 2
One High Basic Construction
Secondary
Compartment
Primary
Compartment
92
MAX.
(6)
CT’S
2/Ø
PV BKR
MAX.
(6)
CT’S
2/Ø
1
AØ
BØ
CØ
1 1/8
GSCT
(OPT)
16 1/2
31 1/2
33 1/2
83 5/8
2) Two-high Construction
The two-high basic construction standard
measurements are 95” height x 36” width
x 95-1/8” depth. This construction can
hold two circuit breakers; one in each
compartment located one above the other.
Note:
Each construction includes primary
and secondary compartments, as
shown in Figure 2 and 3. These
instructions apply to both types of
construction. Where significant
differences exist between the two
construction types, each is explained
separately.
Figure 3
Two-High Basic Construction
1
1 1/8
21 1/2
31 1/2
40
95 1/8
Primary
Compartment
Secondary
Compartment
MAX.
(6)
CT’S
2/Ø
PV BKR
MAX.
(6)
CT’S
2/Ø
MAX.
(6)
CT’S
2/Ø
PV BKR
MAX.
(6)
CT’S
2/Ø
GSCT
(OPT)
GSCT
(OPT)
AØ
BØ
CØ
95
c. p
rImAry
c
ompArtment
The primary compartment contains the high
voltage equipment and connections arranged
in compartments to offer increased safety by
minimizing personnel exposure and limiting
the effects of faults. The primary enclosure
contains control devices, current transformers,
shutters, interlocks, and a ground bus. See
Figure 3 for the location of the primary
enclosure and see Figure 4 for the equipment’s
devices.