13
Equipment Description
01.4IB.51000C
A rollout stop block is provided to deter
the removal of the circuit breaker from the
compartment until the rollout latch on the
circuit breaker is depressed.
Figure 6
Circuit Breaker Cover Removed
a
b
c
d
e
a. TOC Actuator
b. Opening Spring
c. Main Closing Spring
d. MOC Actuator
e. Charging Motor
J. A
uxIlIAry
c
ompArtmentS
Many sizes of auxiliary enclosures and
compartments are furnished for various
purposes in PowlVac® Metal-clad Switchgear
line-ups. Some are listed below:
• Bus transitions to motor controllers
• Bus transitions to transformers
• Cable entrance compartments
• Starting reactor or auto-transformer
compartments
• Relay and metering compartments
• Instrument transformer compartments
• Control power transformer compartments
k. A
ntI
-c
onDenSAtIon
h
eAterS
Anti-condensation heaters are provided in
all PowlVac switchgear in order to facilitate
drying and to prevent condensation. It is
recommended that heaters are energized at all
times; accordingly, no switch or thermostat is
provided in the heater circuit unless specified.
Each one-high basic construction is furnished
with a heater providing 125 watts of heat. Each
two-high basic construction has two such
heaters, for a total of 250 watts of heat. See
Figure 7.
Heaters in circuit breaker compartments are
located on the bottom right of the secondary
compartment, below the lower primary
disconnect devices. Heaters in auxiliary
compartments are located in a similar location.
In auxiliary compartments equipped with
rollouts, it may be necessary to remove the
lower rollout to gain access to the heater.
Figure 7
Unit Space Heater