Equipment Description
01.4IB.51000C
PowlVac® Metal-Clad Switchgear
5kV & 15kV
p. p
rImAry
D
ISconnect
D
evIceS
A
nD
S
upportS
The stationary primary disconnect devices have
flat silver-plated copper contact bars located
within the molded epoxy supports found at
the rear of the circuit breaker compartment,
behind the safety shutters. The rear of the
contact is bolted to the main bus riser or to the
line-side bus. The contacts may be withdrawn
from the rear of the supports when other bus
connections have been removed.
The movable primary disconnects devices (on
the circuit breaker) will engage automatically
with the stationary primary disconnect devices
near the end of the racking cycle. Contact
penetration is set by the racking device and no
additional adjustments should be necessary.
The removable element disconnect contacts
are self-aligning fingers, which will compensate
for minor misalignment of up to approximately
¹⁄8 inch.
Q. l
IGhtInG
For through-door and closed-door racking,
all metal-clad switchgear are equipped with
a 120VAC interior light and a door-mounted
light switch. When the interior light is switched
on in the circuit breaker compartment, the
user can read “breaker test/disconnected” or
“breaker connected” on the circuit breaker
position indicator through the view window.