Powered by Safety
®
30
Installation
01.4IB.51000C
PowlVac® Metal-Clad Switchgear
5kV & 15kV
m. I
nSulAtInG
p
rImAry
c
ABle
t
ermInAtIonS
All field assembled joints for primary cable
terminations should be prepared as outlined
completion of the cable termination, care
must be exercised when taping the exposed
termination.
1. All taping of cable termination joints should
be insulated as outlined Figure 22.
2. All taping of roof bushing should be
insulated as shown in Figure 24. See
for details.
2. The instructions for application of the tape
insulation are the same as outlined for
wrapping of joints. See
Figure 22 Cable Termination Joint
Epoxy Insulation Thermoplastic
Sleeving or Tape Insulation
.50 (12.7)
Min
#6 Cable to Surge Supressors or
Lightening Arrestors Potential
Transf., etc.
.50 (12.7)
Min
“C”
“B”
“A”
“C”
Table I Cable Termination Joint
Insulation
Level
(kV)
Inner
Filler
“A”
Outer
Wrap
“B”
“C”
(inches)
Approx. No. of Rolls per
Joint of HV Tape ∆
2” or 3” Bars
4” or 6” Bars
5 or 15
RB Putty* &
3 Layers HV
Tape ∆
2 Layers
HV Tape ∆
3
½ Roll Putty* &
1 Roll Tape ∆
1 Roll Putty* &
2 Roll Tape ∆
Note:
* Electrical grade rubber-based putty
0282A3529P008 in roll form will be
used to grade voids and smooth out
sharp edges of joints. This putty has
no insulation value.
1 roll is 1/8” x 1
½
” x 5’ long
∆
HV Tape 0282A3529P004 roll is
0.030” x 2” x 30’ long. Apply with
mastic side down.