Powered by Safety
®
42
Operation
01.4IB.51000C
PowlVac® Metal-Clad Switchgear
5kV & 15kV
d. Once the circuit breaker has reached
the connected position, remove the
racking handle, verify that the manual
trip operator has returned to its normal
position, close the compartment door,
and operate the circuit breaker as
required.
Note:
This is the Connected Position.
Figure 31 Racking the Standard Circuit Breaker
a
a. Racking Handle
3) Removing the Circuit Breaker from the
Connected Position
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure that
the control circuits are deenergized.
!
CAUTION
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure the
circuit breaker is in the open position and all
springs are discharged.
!
CAUTION
a. Verify that the circuit breaker
open/closed indicator displays
“
BREAKER OPEN
”. If “
CLOSED
”, close
door and open breaker from a remote
location or alternately by using the
circuit breaker control switch on
compartment door. Open door and
verify that the circuit breaker
open/closed indicator displays
“
BREAKER OPEN
”.
b. With the compartment door open, press
and hold the manual trip operator and
simultaneously open the racking drive
shaft shutter. Place the racking handle
socket onto the racking drive shaft
shutter. The racking handle socket may
be used to push down the shutter to
gain access to the racking drive shaft.
c. Release the manual trip operator. It will
remain actuated as long as the shutter is
held open by the racking handle socket.