9
3-3. Audible Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Bypass Mode
Sounding every 10 seconds
3-4. LCD display wordings index
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
HLS
High loss
LLS
Low loss
BAT
Battery
CF
Converter
TP
Temperature
CH
Charger
FU
Bypass frequency unstable
EE
EEPROM error
BAH
AH of battery
3-5. UPS Setting
There are three parameters to set up the
UPS.
Parameter 1: It’s for program
alternatives. Refer to below table for the
details.
Parameter 2 and parameter 3 are the
setting options or values for each
program.
Parameter 1
Parameter 2
Parameter 3