10
01: Output voltage setting
Interface
Setting
You may choose the following output voltage:
100: presents output voltage is 100Vac
104: presents output voltage is 104Vac
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac(default)
120: presents output voltage is 120Vac
02: Frequency Converter enable/disable
Interface
Setting
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
03: Output frequency setting
Interface
Setting
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50HZ (Default)
BAT 60: presents output frequency is 60HZ
If converter mode enable, you may choose the following
output frequency:
CF 50: presents output frequency is 50HZ (Default)
CF 60: presents output frequency is 60HZ
04: Acceptable input voltage range setting
Interface
Setting
Press the Down key or Up key to set the acceptable high
voltage point and acceptable low voltage point of the input:
HLS: High loss voltage in Line mode
260-300: The setting range is from 260VAC to 300VAC.
(Default 300VAC)
LLS: Low loss voltage in Line mode
160-190: The setting range is from 160VAC to 190VAC.
(Default 160VAC)
05: ECO mode enable/disable
Interface
Setting
ENA: ECO mode enable
DIS: ECO mode disable (Default)