13 

 

Operating mode  Description 

LCD display   

Bypass mode 

When input voltage is within acceptable 
range but UPS is overload, UPS will enter 
bypass mode or bypass mode can be set 

by front panel. Alarm is sounding every 
10 second.   

 

Standby mode 

UPS is powered off and no output supply 
power, but still can charge batteries. 

 

3-7. Faults Reference Code 

Fault event 

Fault code    Icon  Fault event 

Fault code    Icon 

Bus start fail 

01 

Inverter voltage Low 

13 

Bus over 

02 

Inverter output short 

14 

 

Bus under 

03 

Battery voltage too high  27 

 

Bus short-circuited 

05 

Battery voltage too low 

28 

 

Inverter soft start fail 

11 

Over temperature 

41 

Inverter voltage high 

12 

Over load 

43 

 

3-8. Warning indicator 

Warning 

Icon (flashing) 

Alarm 

Low Battery 

 

 

Sounding every second 

Overload 

 

 

Sounding twice every second 

Battery is not connected 

 

 

Sounding every second 

Over Charge 

 

 

Sounding every second 

Site wiring fault 

 

 

Sounding every second 

Over temperature 

 

 

Sounding every second 

Charger failure 

 

 

Sounding every second 

Battery fault 

 

 

Sounding every second 

Battery replacement 

 

 

Sounding every 2 second 

Out of bypass voltage range 

 

 

Sounding every second 

Bypass frequency unstable 

 

 

Sounding every second 

EEPROM error 

 

 

Sounding every second 

Summary of Contents for FRUK19-3000HV-01V

Page 1: ...Online UPS FRUK19 3000HV 01V Uninterruptible Power Supply System User Manual...

Page 2: ...s 3 2 INSTALLATION AND SETUP 4 2 1 Rear Panel View 4 2 2 Setup the UPS 4 3 OPERATIONS 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 9 3 4 LCD display wordings index 9 3 5 UPS Setting 9 3...

Page 3: ...no one can step on or trip over them The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...al package in a safe place for future use 2 1 Rear Panel View Diagram 1 Rear Panel Overlook Diagram 2 Output Terminal 1 Output receptacles 2 Output terminals 3 Bypass switch 4 AC input 5 Input breaker...

Page 6: ...options Step 1 Step 2 Step 3 Remove cover of intelligent slot Insert communication card into the slot Screw card tightly and complete installation Step 4 Turn on the UPS Press the ON Mute button on t...

Page 7: ...ttery capacity configuration in software To calculate accurate backup time of external batteries it s necessary to configure battery numbers in software The standard calculated capacity for one batter...

Page 8: ...he UPS Press and hold this button at least 2 seconds to turn off the UPS Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this bu...

Page 9: ...uency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS con...

Page 10: ...content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter TP Temperature CH Charger FU Bypass frequency unstable EE EEPROM error BAH AH of battery 3 5 UPS...

Page 11: ...presents output frequency is 50HZ Default BAT 60 presents output frequency is 60HZ If converter mode enable you may choose the following output frequency CF 50 presents output frequency is 50HZ Defau...

Page 12: ...oint 230 264 setting the high voltage point from 230VAC to 264VAC Default 264VAC LLS Bypass low voltage point 170 220 setting the low voltage point from 170VAC to 220VAC Default 170VAC 09 Autonomy lim...

Page 13: ...mode Description LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO...

Page 14: ...ry voltage too high 27 Bus short circuited 05 x Battery voltage too low 28 Inverter soft start fail 11 x Over temperature 41 x Inverter voltage high 12 x Over load 43 3 8 Warning indicator Warning Ico...

Page 15: ...ealer Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact your dealer The icon and is flashi...

Page 16: ...ults 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power Contact your dealer Battery backup time is shorter than nominal value Batteries are no...

Page 17: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Page 18: ...e AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 80 81 Battery Mode 82 BATTERY Standard Model Battery Type 12V 9Ah Battery Numbers 6 Char...