4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table 
below.   

Symptom 

Possible cause 

Remedy 

No indication and alarm even 
though the mains is normal.   

The AC input power is not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 
mains.   

The AC input is connected 

to the UPS output. 

Plug  AC  input  power  cord 

to AC input correctly.   

The icon 

and 

  flashing on 

LCD display and alarm is sounding 

every second. 

Line and neutral 
conductors of UPS input 

are reversed. 

Rotate mains power socket 
by  180°  and  then  connect 

to UPS system. 

The icon 

and 

  flashing 

on LCD display and alarm is 
sounding every second. 

The external or internal 
battery is incorrectly 
connected. 

Check  if  all  batteries  are 
connected well. 

Fault code is shown as 27 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery voltage is too high 

or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery  voltage  is  too  low 

or the charger is fault. 

Contact your dealer. 

The icon 

  and

is 

flashing on LCD display and alarm 
is sounding twice every second. 

UPS is overload   

Remove excess loads from 

UPS output. 

UPS is overloaded. Devices 
connected to the UPS are 
fed directly by the 

electrical network via the 
Bypass. 

Remove excess loads from 
UPS output. 

After repetitive overloads, 
the UPS is locked in the 

Bypass mode. Connected 
devices are fed directly by 
the mains. 

Remove excess loads from 
UPS output first. Then shut 

down  the  UPS  and  restart 
it. 

Fault code is shown as 43 and The 

icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

The UPS shut down 

automatically because of 
overload at the UPS 
output. 

Remove excess loads from 

UPS output and restart it. 

Fault code is shown as 14 and the 
icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

The UPS shut down 
automatically because 
short circuit occurs on the 

UPS output. 

Check output wiring and if 
connected  devices  are  in 
short circuit status. 

Summary of Contents for FRUK19-3000HV-01V

Page 1: ...Online UPS FRUK19 3000HV 01V Uninterruptible Power Supply System User Manual...

Page 2: ...s 3 2 INSTALLATION AND SETUP 4 2 1 Rear Panel View 4 2 2 Setup the UPS 4 3 OPERATIONS 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 9 3 4 LCD display wordings index 9 3 5 UPS Setting 9 3...

Page 3: ...no one can step on or trip over them The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...al package in a safe place for future use 2 1 Rear Panel View Diagram 1 Rear Panel Overlook Diagram 2 Output Terminal 1 Output receptacles 2 Output terminals 3 Bypass switch 4 AC input 5 Input breaker...

Page 6: ...options Step 1 Step 2 Step 3 Remove cover of intelligent slot Insert communication card into the slot Screw card tightly and complete installation Step 4 Turn on the UPS Press the ON Mute button on t...

Page 7: ...ttery capacity configuration in software To calculate accurate backup time of external batteries it s necessary to configure battery numbers in software The standard calculated capacity for one batter...

Page 8: ...he UPS Press and hold this button at least 2 seconds to turn off the UPS Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this bu...

Page 9: ...uency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS con...

Page 10: ...content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter TP Temperature CH Charger FU Bypass frequency unstable EE EEPROM error BAH AH of battery 3 5 UPS...

Page 11: ...presents output frequency is 50HZ Default BAT 60 presents output frequency is 60HZ If converter mode enable you may choose the following output frequency CF 50 presents output frequency is 50HZ Defau...

Page 12: ...oint 230 264 setting the high voltage point from 230VAC to 264VAC Default 264VAC LLS Bypass low voltage point 170 220 setting the low voltage point from 170VAC to 220VAC Default 170VAC 09 Autonomy lim...

Page 13: ...mode Description LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO...

Page 14: ...ry voltage too high 27 Bus short circuited 05 x Battery voltage too low 28 Inverter soft start fail 11 x Over temperature 41 x Inverter voltage high 12 x Over load 43 3 8 Warning indicator Warning Ico...

Page 15: ...ealer Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact your dealer The icon and is flashi...

Page 16: ...ults 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power Contact your dealer Battery backup time is shorter than nominal value Batteries are no...

Page 17: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Page 18: ...e AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 80 81 Battery Mode 82 BATTERY Standard Model Battery Type 12V 9Ah Battery Numbers 6 Char...

Reviews: