background image

4.  Gas High Fire Input Cannot Be Achieved
 

A.  Gas company pressure regulator or meter  

 

 

 

operating incorrectly, not allowing required gas  

 

 

pressure at burner train inlet. Have gas company  

  correct.
 

B.  Gas cock upstream of train inlet not fully open.  

 

 

Check and correct.

 

C.  Gas line obstructed. Check and correct.

 

D.  Gas train main and/or leak test cocks not fully  

 

 

open. Check and correct.

 

E.  Gas supply line between gas company regulator  

 

 

and burner inlet too small. Check supply pressure  

 

 

at meter, determine pressure drop and increase  

 

 

line size as required, or raise supply pressure to  

 

 

compensate for small line. Do not raise pressure  

 

 

so high that under static (no flow) conditions the  

 

 

pressure exceeds the maximum allowable  

 

 

 

pressure to the gas train components on the burner.

 

F.  Burner gas train components sized too small for  

 

 

supply pressure. Increase component size as   

  appropriate.
 

G.  Automatic gas valve not opening fully due to    

 

 

defective operation. Replace gas valve.

 

H.  Side tee (limiting) orifice (if supplied) too small.  

 

 

Replace with correct size.

 

I.  On modulating burner, butterfly valve not fully   

 

 

opened. Readjust.

 

J.  Defective main gas pressure regulator. Replace.

 

K.  Incorrect spring in main gas pressure regulator.  

 

 

Replace as required.

 

L.  Main gas pressure regulator vent line obstructed.  

 

 

Check and correct.

 

M.  Normally open vent valve (if supplied) not closing  

 

 

when automatic gas valves open. Check to see if  

 

 

valve is fully closed when automatic valves are  

 

 

open. Replace vent valve, if not closing fully.

OIL OPERATION

1.  Burner Motor Runs, but Direct Spark Ignited Oil  

 

Flame is Not Established

 

A.   Defective or incorrect size oil nozzle. Remove and  

 

    clean or replace.

 

B.   Low oil pressure. Check with gauge for correct  

 

   light-off pressure.

 

C.   Defective oil pump. Replace.

 

D.   Defective oil solenoid valve. Replace.

 

E.   Oil pump coupling loose or defective. Replace or  

 

    tighten as required.

 

F.   Low oil pressure switch (if supplied) defective or  

 

    incorrectly set. Adjust or replace switch.

 

G.   Ignition transformer defective. Replace.

 

H.   Ignition electrode set incorrectly. Remove electrodes  

 

    and reset.

 

I.    Ignition electrodes cracked and grounding out  

 

    spark. Replace electrodes.

 

J.    Ignition leadwire defective and grounding spark out.   

 

   Replace.

 

K.   Ignition plug in connections at transformer or   

 

    electrodes loose. Tighten.

 

L..  Air flow switch (if provided) not making. Reset  

 

    pressure or replace.

 

M.  Defective flame safeguard control or plug in    

 

    purge timer card. Replace.

 

N.   Air dampers held in high fire position due to    

 

    mechanical binding of linkage. Readjust linkage.

 

O.   Loose wiring connections. Check and tighten all  

 

   connections.

2.  Oil Flame Ignites, but then Flame Safeguard    

 

Control Locks Out on Safety

 

A.   Flame scanner lens dirty. Remove and clean.

 

B.   Scanner sight tube blocked or dirty. Check and  

 

   clean.

 

C.   Flame scanner defective. Replace.

 

D.   Defective oil nozzle causing unstable flame and  

 

    scanning problems. Replace oil nozzle.

 

E.   Fuel/air ratios incorrect, resulting in unstable or  

 

    smoky flame causing scanner flame sighting    

 

    problem. Readjust ratios for clean stable flame.

 

F.   Defective flame safeguard amplifier or control.   

 

    Replace as appropriate.

3.  Oil Flame Extremely Smoky at Light Off or in Low  

 

Fire Position

 

A.   Defective or incorrect size oil nozzle. Replace.

 

B.   Fuel/air ratio incorrect. Readjust.

 

C.   N.C. oil solenoid valve in oil nozzle return line not  

 

    opening. Check electrical circuitry and replace  

 

    valve if defective.

 

D.   On two-step pump - N.O. pump mounted solenoid  

 

    valve malfunctioning. Replace valve or pump.

4.  Light Off Oil Flame Is Established and Proven, but  

 

Burner Will Not Attempt to Go to the High  

 

Fire Position

 

A.   Low/High/Low or Modulating burner high fire    

 

    temperature or pressure control could be  

 

    defective or not set to call for high fire. Readjust  

 

    or replace control.

 

B.   Loose wires or incorrectly wired. Verify wiring and  

 

    tighten all connections.

 

C.   Flame safeguard control or high fire panel  

 

 

    switching relay (if supplied) defective. Verify and  

 

    correct as required.

 

D.   High fire 3 way solenoid valve defective. Replace.

 

E.   Hydraulic oil cylinder defective. Replace.

 

F.   On two-step pump - N.O. solenoid valve defective  

 

    (not closing). Replace pump or valve.

 

G.   Linkage mechanically binding.  Readjust linkage.

 

H.   On modulating system - defective modulating   

 

    motor. Replace.

5.  Low Oil Flame Is Established and Proven, but Flame  

 

Out Occurs in Transition from Low Fire to High Fire

 

A.   On Low/High/Off or Low/High/Low system - N.C.  

 

    oil solenoid valve in nozzle return line not closing  

 

    (or leaking). Check valve operation and replace  

 

    if necessary.

 

B.   On two-step oil pump - N.O. solenoid valve    

 

    defective (not closing). Replace valve or pump.

 

C.   Defective or incorrect size oil nozzle. Replace.

 

D.   High fire oil pressure too low. Readjust.

 

E.   Air dampers set too far open at low fire, which  

 

      causes flame to blow out in starting to high fire.   

 

    Readjust dampers.

 

F.   Oil pump coupling loose or defective. Tighten  or  

 

   replace.

 

G.   Defective oil pump. Replace.

 

H.   Linkage mechanically binding. Readjust.

 

I.    Make certain the #72 orifice into the N.C. side of  

 

    the 3 way valve has not been removed.

 

J.   On modulating systems - fuel/air ratios set  

 

 

    incorrectly, causing flame to blow out when  

 

    going to high fire. Readjust linkage.

C43

Rev.304

TROUbLE ShOOTING SUGGESTIONS 

GAS, OIL OR GAS/OIL bURNER

Summary of Contents for C1-GO-10

Page 1: ...C MANUAL POWER FLAME INCORPORATED...

Page 2: ...6 Removable Total Access Door 27 Optional Board for Sequence Indicator Lights The computer generated Burner Specification Sheets shipped with the burner represent the as built version of your specific...

Page 3: ...fore starting up the system all appropriate air and oil leak tests should be performed Make certain that the tank atmospheric vent line is unobstructed Refer to page 12 Figure 11 for fuel pump oil pip...

Page 4: ...valves etc Suction line vacuum values for such compo nents vary by manufacturer A Rule of Thumb to determine total vacuum for suction line sizing is to add 10 to vacuum determined from Figure 10 calcu...

Page 5: ...r calls for low fire the normally closed Oil Solenoid Return Valve 7 closed at high fire is energized reducing nozzle pressure to the low fire rate Simultaneously the Three Way Solenoid Valve 10 is de...

Page 6: ...trol Mode Using a Two Step Oil Pump Model C O Field Piped Check Valve At Tank Fuel Shutoff Valve Fusible Link Valve If Required by Code Check Valve Field Piped 12 pressure setting of the pump low fire...

Page 7: ...urn Pressure Tap 8 5 Metering Valve 7 1 8 Allen Screw For Oil Nozzle Pressure Adjustment Under Cap Vacuum Gauge Inlet Port Optional Return Port For Simplex Nozzle Use Alternate Connec tion to Tee on O...

Page 8: ...us tion chambers or high heat release pressurized fireboxes Moving the adjustment knob back increases the premix air Gas Oil Linkage Adjustment For Full Modulation Standard System Typical general link...

Page 9: ...als is for factory use only and should not be used for incoming power connections 2 Close main and checking gas cocks Open suction line manual oil valves and others as appropriate 3 Tighten all screws...

Page 10: ...uit the particular operating conditions 3 Do not secure flame safeguard control into its wiring base until it has been determined that there are no shorts or grounds in the system 4 Install oil pressu...

Page 11: ...chamber 18 For small On Off burners with a simplex nozzle adjustments consist primarily of attaining correct fuel air ratios Adjustments should be set to obtain11 121 2 CO2 and no more than a 2 smoke...

Page 12: ...rm in the boiler or follow specific initial firing recommendations provided by the heat exchanger manufacturer 34 Tighten all linkages and permanently mark settings 35 Limit control check should be ma...

Page 13: ...sure gauges overhead oil lines or fittings A leaking check valve on the bypass return line from the nozzle can create the same effect 6 The Teflon seal should stay on the nozzle when servicing On some...

Page 14: ...2 Fuel Oil By Pass Return Closed Approx High Fire Rate GPH 300 PSIG By Pass Return Closed Approx High Fire By Pass Return Pressure PSIG By Pass Return Closed Approx By Pass Return Pressure PSIG Appro...

Page 15: ...eturn and Firing Rates Will be Reduced Somewhat Consult Factory for Further Information When Supply Pressure to Nozzle is Lower Than 300 PSIG the By Pass Return and Firing Rates Will be Reduced Somewh...

Page 16: ...lon seal in the Monarch F80BPS and Delavan 33769 nozzles is an integral part of the nozzles and that if the seal is removed accidentally the nozzle must be replaced On the Delavan 30630 and 30637 nozz...

Page 17: ...ulators should be kept clean and must be replaced if cracked 2 The spark gap must be set in accordance with the dimensions noted Refer to Figures 30 31 32 Ensure that the distance between the electrod...

Page 18: ...Setting 1 16 Blade Tips After Adj Must be Within 1 16 of A Flat Plane Mark Pipe With Saw For Full Forward Pilot Extends Thru Diffuser 0 125 1 8 5 32 Diameter Orifice Gas Inlet Oil Nozzle Choke Assembl...

Page 19: ...e or check valve not holding Correct as required GAS OPERATION 1 Burner Motor Runs but Pilot Does Not Light A Gas supply to burner shut off make sure all manual gas supply valves are open Automatic hi...

Page 20: ...echanical binding of linkage Readjust linkage O Loose wiring connections Check and tighten all connections 2 Oil Flame Ignites but then Flame Safeguard Control Locks Out on Safety A Flame scanner lens...

Page 21: ...f necessary F On two step pump N O pump mounted oil solenoid valve defective not closing Replace valve or pump G Oil pump coupling loose slipping or defective Replace H Linkage mechanically binding Re...

Page 22: ...turer s instructions Refractory hold in As required annually Service Technician See Pilot turndown tests High limit safety control Annually Service Technician Refer to heat exchanger manufacturer s in...

Reviews: