background image

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

7

10.

COMBUSTION CHAMBER – GENERAL

Certain types of heat exchangers, such as warm air furnaces, some hot oil heaters, wet base

steel, packaged firebox boilers and Scotch Marine boilers, use the combustion chamber to

transfer heat and therefore do not require refractory of other insulation. If in doubt, consult the

heat exchanger equipment manufacturer.

All possible points of air infiltration or ex-filtration must be sealed. If the unit is to be fired under

positive combustion chamber conditions, extreme care must be taken to ensure that a 100%

seal is maintained. The Model NVC burner is designed to provide all the air required for

complete and efficient combustion. Entry or loss of air from sources other than the firing unit will

decrease its’ overall combustion and operational efficiency.

Figure 4

Chamber Dimension Charts

Scotch Marine Boiler Minimum Furnace Tube Inside Diameters

BHP

Min. Inside Dimension

50

20”

100

26”

200

29”

300

34”

400

38”

500

38”

600

42”

700

45”

800

50”

900

50”

1000

50”

1200

54”

1500

54”

Note: The above dimensions are recommended minimums. If boiler dimensions are less than

indicated, consult with the factory.

Combustion chambers shall be provided as recommended, 

Refer to Figure 4

, of Chamber 

Dimension Charts.  A minimum of six inches must be maintained around the burner element.

20

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

Item

Frequency

Checked By

Remarks

Flame signal strength

Weekly

Operator

If flame signal meter installed, read and log;

for both pilot and main flames, notify service

organization if readings are very high, very low,

or fluctuating; refer to flame safeguard

manufacturer’s instructions

Pilot turndown tests

as required/annually

Service Technician

Required after any adjustments to flame

scanner mount or pilot burner; verify annually –

refer to flame safeguard manufacturer’s

instructions.

Refractory hold in

As required/annually

Service Technician

See Pilot Turndown Tests

High limit safety control

Annually

Service Technician

Refer to heat exchanger manufacturer’s

instructions

Operating control

Annually

Service Technician

Refer to heat exchanger manufacturer’s

Instructions

Low draft, fan, air pressure,

Monthly

Operator

Refer to this manual and control manufacturer’s

and damper

instructions

High & low gas pressure interlocks

Monthly

Operator

Refer to instructions in this manual

Fuel valve interlock switch

Annually

Service Technician

Refer to valve manufacturer’s instructions

Purge switch

Annually

Service Technician

Refer to fuel/air control motor manufacturer’s

instructions

Low fire start interlock

Annually

Service Technician

Refer to fuel/air control motor manufacturer’s

instructions

Automatic changeover control

At least annually

Service Technician

Under supervision of gas utility

(dual fuel)

Inspect burner components

Service Technician

Refer to this manual and control component

Manufacturer’s instructions

Check blower motor and blower

Annually

Service Technician

Remove and clean

wheel for cleanliness. Remove

and clean as necessary

Remove, inspect and clean gas

Annually

Service Technician

Remove and clean

pilot assembly

Refer to heat exchanger manufacturer’s instructions for general inspection procedures and for specific

testing and inspection of all liquid level controls, pressure/temperature relief and other applicable items.

If you have any questions about the procedures listed above or questions relating to components or

devices on your unit not specifically covered in the above, contact our Service Department at

(620) 421-0480 for assistance.

16. MAINTENANCE

General Information

Only qualified service technicians should make mechanical or electrical adjustments to the

burner and/or associated control equipment.

Preventive maintenance can usually be performed by building maintenance or operating

personnel.

Always follow the information provided in the Owner Operating Instructions on

page 26.

These

should be conspicuously posted in the burner room at the time of the initial burner installation

and startup.

Always turn the power supply off to the burner and close manual fuel valves as appropriate for

routine maintenance.

Make sure that combustion and ventilation fresh air sources to the burner room remain clean

and open.

Periodically check all electrical connections and make sure the flame safeguard control chassis

is firmly connected to its wiring base.

Refer to manufacturer’s product bulletins supplied with the burner for maintenance on the flame

safeguard control and other components.

PERIODIC CHECK LIST

Item

Frequency

Checked By

Remarks

Gages, monitors and indicators

Daily

Operator

Make visual inspection and record

Readings in log

Combustion Air Filter

Daily

Operator

Make visual inspection of filter and indicator light

Instrument and equipment

Daily

Operator

Make visual check against heat exchanger

settings

manufacturer’s recommended specifications

Firing rate control

Weekly

Operator

Verify heat exchanger manufacture’s settings

Semiannually

Service Technician

Verify heat exchanger manufacture’s settings

Annually

Service Technician

Check with combustion test

Flue, vent, stack or outlet damper

Monthly

Operator

Make visual inspection of linkage, check for

Proper operation

Combustion air

Monthly

Operator

All sources remain clean and open

Ignition System

Weekly

Operator

Make visual inspection, check flame signal

Strength if meter-fitted

(see Combustion Safety Controls)

Fuel Valves

Pilot and main

Weekly

Operator

Open limit switch-make aural and visual check

Check valve position indicators and check

Fuel meters if so fitted

Pilot & main gas

Annually

Service Technician

Perform leakage tests – refer to valve

manufacturer’s instructions

Combustion safety controls

Flame failure

Weekly

Operator

Close manual fuel supply for (1) pilot, (2) main

fuel cock, and/or valve(s) check safety

shutdown timing; log

Summary of Contents for Nova Plus

Page 1: ...Copyright 2006 Power Flame Incorporated Printed in U S A Power F 4 DRAFT CONTROL ENTER ESC Power Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual ...

Page 2: ...witches 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R...

Page 3: ...s 6 9 Burner Mounting General 6 10 Combustion Chamber General 7 11 General Start Up Procedures 8 12 Burner Start Up and Service Test Equipment Required 10 13 Burner Start Up Sequence Instructions 10 14 Gas Pilot Ignition Adjustment 15 15 Trouble Shooting Suggestions 16 16 Maintenance 19 17 Burner Startup Information Test Data 22 18 Owner Operating Instructions 26 NOVA PLUS Installation Operation M...

Page 4: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 5: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 6: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 7: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 8: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 9: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 10: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 11: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 12: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 13: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 14: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 15: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 16: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 17: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 18: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 19: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 20: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 21: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 22: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 23: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 24: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 25: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 26: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 27: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 28: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 29: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 30: ... 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R For us...

Page 31: ...er Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual Power Flame Incorporated 2001 South 21st Street Parsons KS 67357 Telephone 620 421 0480 FAX 620 421 0948 Product Support 620 820 8301 Website http www powerflame com e mail CSD powerflame com ...

Reviews: