background image

19

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

16. MAINTENANCE

General Information

Only qualified service technicians should make mechanical or electrical adjustments to the

burner and/or associated control equipment.

Preventive maintenance can usually be performed by building maintenance or operating

personnel.

Always follow the information provided in the Owner Operating Instructions on

page 26.

These

should be conspicuously posted in the burner room at the time of the initial burner installation

and startup.

Always turn the power supply off to the burner and close manual fuel valves as appropriate for

routine maintenance.

Make sure that combustion and ventilation fresh air sources to the burner room remain clean

and open.

Periodically check all electrical connections and make sure the flame safeguard control chassis

is firmly connected to its wiring base.

Refer to manufacturer’s product bulletins supplied with the burner for maintenance on the flame

safeguard control and other components.

PERIODIC CHECK LIST

Item

Frequency

Checked By

Remarks

Gages, monitors and indicators

Daily

Operator

Make visual inspection and record

Readings in log

Combustion Air Filter

Daily

Operator

Make visual inspection of filter and indicator light

Instrument and equipment

Daily

Operator

Make visual check against heat exchanger

settings

manufacturer’s recommended specifications

Firing rate control

Weekly

Operator

Verify heat exchanger manufacture’s settings

Semiannually

Service Technician

Verify heat exchanger manufacture’s settings

Annually

Service Technician

Check with combustion test

Flue, vent, stack or outlet damper

Monthly

Operator

Make visual inspection of linkage, check for

Proper operation

Combustion air

Monthly

Operator

All sources remain clean and open

Ignition System

Weekly

Operator

Make visual inspection, check flame signal

Strength if meter-fitted

(see Combustion Safety Controls)

Fuel Valves

Pilot and main

Weekly

Operator

Open limit switch-make aural and visual check

Check valve position indicators and check

Fuel meters if so fitted

Pilot & main gas

Annually

Service Technician

Perform leakage tests – refer to valve

manufacturer’s instructions

Combustion safety controls

Flame failure

Weekly

Operator

Close manual fuel supply for (1) pilot, (2) main

fuel cock, and/or valve(s) check safety

shutdown timing; log

F.

Main gas pressure regulator atmospheric vent line obstructed. Correct.

G.

Defective main gas pressure regulator – replace. Misadjusted main gas pressure

regulator – readjust to meet required operational values.

5.

Carbon Monoxide Readings Too High

A.

Flame impingement on cold heat transfer surfaces caused by excessive firing

rate. Reduce firing rate to correct input volume.

B.

Flame impingement on cold combustion chamber surfaces due to undersized

combustion chamber. Refer to chamber size charts, page 10, and/or contact

factory for additional information.

C.

Incorrect gas/air ratios. Readjust burner to correct CO

2

 / O

2

levels, reducing CO

formation to appropriate level.

6.

High Fire Input Cannot Be Achieved

A.

Gas company pressure regulator or meter operating incorrectly, not allowing

required gas pressure at burner train inlet. Have gas company correct.

B.

Gas cock upstream of train inlet not fully open. Check and correct.

C.

Gas line obstructed. Check and correct.

D.

Gas train main and/or leak test cocks not fully open. Check and correct.

E.

Gas supply line between gas company regulator and burner inlet too small.

Check supply pressure at meter, determine pressure drop and increase line size

as required, or raise supply pressure to compensate for small line. Do not raise

pressure so high that under static (no flow) conditions the pressure exceeds the

maximum allowable pressure to the gas train components on the burner.

F.

Burner gas train components sized too small for supply pressure. Increase

component size as appropriate.

G.

Automatic gas valve not opening fully due to defective operation. Replace gas

valve.

H.

Butterfly valve not fully opened. Readjust.

I.

Defective main gas pressure regulator. Replace

J.

Incorrect spring in main gas pressure regulator. Replace as required.

K.

Main gas pressure regulator vent line obstructed. Check and correct.

L.

Normally open vent valve (if supplied) not closing when automatic gas valves

open. Check to see if valve is fully closed when automatic valves are open.

Replace vent valve, if not closing fully.

8

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

11. GENERAL START UP PROCEDURES

General Start Up

A thoroughly qualified burner technician must be employed to provide the initial burner start up,

as well as any subsequent servicing of the burner and related controls.

A representative of the owner and/or the person or persons responsible for operating and

maintaining the unit should be present during the initial start up. A service representative may

also be required by the local utility on gas-fired equipment. Instructions regarding the proper

care and maintenance of the unit should be outlined with these people present.

Before initiating start up, the start up technician should thoroughly study and become completely

familiar with the exact sequence of operation and all other details of the specific flame

safeguard control system being used. This information will be found in bulletins printed and

supplied by Autoflame, Honeywell, Fireye, or Siemens. A copy of this bulletin is supplied with

the burner in the Owners/Installers Packet.

After the burner is mounted and all wiring and piping has been completed, tested and determined to

be correct, the following procedures are recommended:

1. Make a general inspection of the equipment room to ensure that the installation is complete.

Check piping, controls, wiring and etc.

2. Close main and checking gas cocks.

3. Tighten all screws on terminal blocks in control cabinet in case some may have loosened in

shipment.

4. Check fuses in main panel (if supplied) and in burner control cabinet. Check wiring to the

burner control cabinet for compliance with the wiring diagram and local codes. Determine that

voltage supply is correct to motor starter line connections and to control circuit line connections.

If a control circuit transformer is supplied, make certain its primary voltage matches the line

voltage being supplied. (A 230 volt transformer does not produce proper control voltage when

supplied with 208 volts).

5. Check breaching and stack to ensure that they are open and unobstructed.

6. Check blower rotation by momentarily making contact of the motor starters. Proper rotation is

imprinted on the fan housing.

7. Check operating controls, limit controls, low water cut-off, flame safeguard control reset, high

and low gas pressure switches (if used), low fire interlock switch (if used) and all other

applicable interlocks. All contacts should be closed (an exception will be found on jobs using

the low gas pressure switch; this switch should be open until the main gas cock is opened).

8. Do not repeatedly recycle the burner, as to allow any unburned fuel in the combustion chamber

to collect. Allow 5 minutes between recycles.

9. Specific instructions relative to component sequencing are provided in the flame safeguard

manufacturer’s bulletin which is included with the documentation shipped with the burner.

Summary of Contents for Nova Plus

Page 1: ...Copyright 2006 Power Flame Incorporated Printed in U S A Power F 4 DRAFT CONTROL ENTER ESC Power Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual ...

Page 2: ...witches 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R...

Page 3: ...s 6 9 Burner Mounting General 6 10 Combustion Chamber General 7 11 General Start Up Procedures 8 12 Burner Start Up and Service Test Equipment Required 10 13 Burner Start Up Sequence Instructions 10 14 Gas Pilot Ignition Adjustment 15 15 Trouble Shooting Suggestions 16 16 Maintenance 19 17 Burner Startup Information Test Data 22 18 Owner Operating Instructions 26 NOVA PLUS Installation Operation M...

Page 4: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 5: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 6: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 7: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 8: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 9: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 10: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 11: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 12: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 13: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 14: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 15: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 16: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 17: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 18: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 19: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 20: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 21: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 22: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 23: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 24: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 25: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 26: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 27: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 28: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 29: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 30: ... 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R For us...

Page 31: ...er Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual Power Flame Incorporated 2001 South 21st Street Parsons KS 67357 Telephone 620 421 0480 FAX 620 421 0948 Product Support 620 820 8301 Website http www powerflame com e mail CSD powerflame com ...

Reviews: