background image

9

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

10. Proper test equipment must be used in order to achieve maximum system operational reliability

and fuel efficiencies.

See page 10, item 12 for equipment lists.

11. All fuel/air adjustments should be made to achieve required input rate, satisfactory combustion

test values, flame stability and appearance. Before start up determine the burner’s manifold

pressure, see

Figure 5

, (Approximate High Fire Manifold Pressure). The pressures shown

(Total) are the approximate net pressure, therefore the heat exchanger’s over-fire pressure

must be added to these pressures for the total manifold pressure.

Figure 5

Approximate High Fire Manifold Pressures

Burner

Mixing Spool

Firing

Model

Orifice Qty/Size

Rate CFH

Or Element =

Total

NVC2

(8).313

2,000

3.86”

5”

8.8

NVC3 (20)

(8).344

2,500

4.17”

5”

9.1

NVC3 (25)

(8).375

3,000

4.24”

5”

9.2

NVC3 (25B)

(8).406

3,500

4.15”

5”

9.2

NVC4

(6).577, (6).531

5,000

1.16”

5”

6.2

NVC5A

(6).577, (6).531

5,520

1.42”

5”

6.4

NVC5

(6).577, (6).531

7,000

2.29”

5”

7.3

NVC6A

(6).577, (6).531

8,400

3.29”

5”

8.3”

NVC6

(6).577, (6).531

10,500

5.15”

5”

10.2

NVC7

(6).620, (6).531

12,600

5.85”

5”

10.9

NVC8

(6).620, (6).531

14,700

7.98”

5”

13.0

NVC9

(8).646, (8).625

16,800

3.98”

5”

9.0

NVC10A

(8).646, (8).625

18,860

5.00”

5”

10.0”

NVC10

(8).646, (8).625

21,000

6.21”

5”

11.2

NVC11

(8).646, (8).625

25,200

8.9”

5”

13.9

NVC12

(20).709

29,400

5.0”

5”

10.0

NVC13

(20).709

33,600

6.58”

5”

11.6

NVC14

(16).834

37,800

6.8”

5”

11.8

NVC15

(16).834

42,000

8.45”

5”

13.5

NVC16

(16).834

50,400

12.16”

5”

17.1

NVC17

(16).834

63,000

19.01”

5”

24.0

12. Every new burner startup should employ the use of the Burner Start Up Information and Test

Data sheets on

page 22.

The gas system uses two motorized gas shutoff valves to control the on/off flow of the gas. A

modulating motor or servo motor (depending on the control scheme) controls the positioning of

a butterfly type Gas Proportioning Valve. When the modulating motor is employed it also

controls the positioning of the combustion air dampers, while a second servo will control the air

dampers when servos are used.

18

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

F.

Main gas pressure regulator atmospheric vent line obstructed. Correct.

G.

Defective main gas pressure regulator – replace. Misadjusted main gas pressure

regulator – readjust to meet required operational values.

5.

Carbon Monoxide Readings Too High

A.

Flame impingement on cold heat transfer surfaces caused by excessive firing

rate. Reduce firing rate to correct input volume.

B.

Flame impingement on cold combustion chamber surfaces due to undersized

combustion chamber. Refer to chamber size charts, page 10, and/or contact

factory for additional information.

C.

Incorrect gas/air ratios. Readjust burner to correct CO

2

 / O

2

levels, reducing CO

formation to appropriate level.

6.

High Fire Input Cannot Be Achieved

A.

Gas company pressure regulator or meter operating incorrectly, not allowing

required gas pressure at burner train inlet. Have gas company correct.

B.

Gas cock upstream of train inlet not fully open. Check and correct.

C.

Gas line obstructed. Check and correct.

D.

Gas train main and/or leak test cocks not fully open. Check and correct.

E.

Gas supply line between gas company regulator and burner inlet too small.

Check supply pressure at meter, determine pressure drop and increase line size

as required, or raise supply pressure to compensate for small line. Do not raise

pressure so high that under static (no flow) conditions the pressure exceeds the

maximum allowable pressure to the gas train components on the burner.

F.

Burner gas train components sized too small for supply pressure. Increase

component size as appropriate.

G.

Automatic gas valve not opening fully due to defective operation. Replace gas

valve.

H.

Butterfly valve not fully opened. Readjust.

I.

Defective main gas pressure regulator. Replace

J.

Incorrect spring in main gas pressure regulator. Replace as required.

K.

Main gas pressure regulator vent line obstructed. Check and correct.

L.

Normally open vent valve (if supplied) not closing when automatic gas valves

open. Check to see if valve is fully closed when automatic valves are open.

Replace vent valve, if not closing fully.

E.

Occasional low voltage supply. Have local utility correct. Make certain that the

burner control circuit transformer (if supplied) is correct for the voltage being

supplied.

F.

Occasional low gas supply pressure. Have utility correct.

G.

Element air pressure switch opens during purge. Reset switch to remain closed

just under maximum purge pressure.

3.

Burner Motor Runs, but Pilot Does Not Light

A.

Gas supply to burner shut off – make sure all manual gas supply valves are

open. Automatic high pressure valve at meter such as Sentry type tripped shut

due to high gas pressure – reset valve and correct cause for trip out.

B.

Pilot solenoid valve not opening – listen and feel for valve actuation. Solenoid

valve not being powered – check electrical circuitry. Replace coil or entire valve

if coil is burned out.

C.

Defective gas pilot regulator – replace.

D.

Gas pressure too high or too low at pilot orifice. Check orifice size in gas pilot

assembly. Replace if incorrect. Refer to gas pilot adjustments for correct

settings. Readjust as required.

E.

Defective ignition transformer – replace. Incorrect ignition electrode settings –

refer to gas pilot adjustments for correct settings.

F.

Defective flame safeguard control or plug in purge timing card. Replace as

required.

G.

Air flow switch not making circuit – check out electrically and correct pressure

adjustment on switch, if required. Defective air flow switch – replace. Air switch

negative pressure sensing tube out of position – reposition as necessary.

4.

Burner Motor Runs and Pilot Lights, but Main Gas Flame Is Not Established

A.

Main shutoff or test cock closed. Check to make certain fully open.

B.

Pilot flame signal reading too low to pull in flame safeguard relay. Refer to gas

pilot settings section and readjust as required.

C.

Defective automatic main or auxiliary gas shut off valves. Check electrical

circuitry to valves. Replace valves or correct circuitry as required.

D.

Defective flame safeguard control or plug in amplifier. Check and replace as

required.

E.

Butterfly valve set incorrectly on modulating burner. Readjust as required.

Summary of Contents for Nova Plus

Page 1: ...Copyright 2006 Power Flame Incorporated Printed in U S A Power F 4 DRAFT CONTROL ENTER ESC Power Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual ...

Page 2: ...witches 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R...

Page 3: ...s 6 9 Burner Mounting General 6 10 Combustion Chamber General 7 11 General Start Up Procedures 8 12 Burner Start Up and Service Test Equipment Required 10 13 Burner Start Up Sequence Instructions 10 14 Gas Pilot Ignition Adjustment 15 15 Trouble Shooting Suggestions 16 16 Maintenance 19 17 Burner Startup Information Test Data 22 18 Owner Operating Instructions 26 NOVA PLUS Installation Operation M...

Page 4: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 5: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 6: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 7: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 8: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 9: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 10: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 11: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 12: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 13: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 14: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 15: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 16: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 17: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 18: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 19: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 20: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 21: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 22: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 23: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 24: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 25: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 26: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 27: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 28: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 29: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 30: ... 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R For us...

Page 31: ...er Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual Power Flame Incorporated 2001 South 21st Street Parsons KS 67357 Telephone 620 421 0480 FAX 620 421 0948 Product Support 620 820 8301 Website http www powerflame com e mail CSD powerflame com ...

Reviews: