NOVA PLUS Installation & Operation Manual -
POWER FLAME INCORPORATED
DC4 DRAFT CONTROL
ENTER
ESC
®
5
Refer to Table 1
for information relating to the sizing of gas supply piping. These charts are
based on the general flow characteristics of commercially produced black carbon steel pipe. If
in doubt regarding flow capabilities of a chosen line size, the next largest size is recommended.
Refer to Figure 3
for the typical gas piping schematic to meet U.L. requirements in the NVC
burner firing ranges.
Table 1
Table 1A
Capacity of Pipe – Natural Gas (CFH)
With Pressure Drop of 0.3” w.c. and Specific Gravity of 0.60
Correction Factors
Pipe Size – Inches (IPS)
Specific Gravity
Other Than 0.60
Specific Drop
Than 0.3
Pipe Length
In Feet
1
1-1/4
1-1/2 2
2-1/2
3
4
10
520 1050
1600 3050 4800
8500
17500
Specific
Gravity
Multiplier
Pressure
Drop
Multiplier
20
350 730
1100 2100 3300
5900
12000
30
285 590
890
1650 2700
4700
9700
0.50
1.10
0.1
0.577
40
245 500
760
1450 2300
4100
8300
0.60
1.00
0.2
0.815
50
215 440
670
1270 2000
3600
7400
0.70
0.926
0.3
1.00
60
195 400
610
1150 1850
3250
6800
0.80
0.867
0.4
1.16
70
180 370
560
1050 1700
3000
6200
0.90
0.817
0.6
1.42
80
170 350
530
990
1600
2800
5800
1.00
0.775
0.8
1.64
90
160 320
490
930
1500
2600
5400
Propane - Air
1.0
1.83
100
150 305
460
870
1400
2500
5100
1.10
0.740
2.0
2.58
125
130 275
410
780
1250
2200
4500
Propane
3.0
3.16
150
120 250
380
710
1130
2000
4100
1.55
0.662
4.0
3.65
175
110 225
350
650
1050
1850
3800
Butane
6.0
4.47
200
100 210
320
610
980
1700
3500
2.00
0.547
8.0
5.15
Note: Use multiplier at right for other specific gravities and pressure drops.
Table 2
Equivalent Length of Fittings in Feet
Pipe Size (IPS)
1.0
1.25
1.5
2
2.5
3
4
Std tee through side
5.5
7.5
9.0
12.0
14.0
17.0
22.0
Std. E11
2.7
3.7
4.3
5.5
6.5
8.0
12.0
45
°
E11
1.2
1.6
2.0
2.5
3.0
3.7
5.0
Plug Cock
3.0
4.0
5.5
7.5
9.0
12.0
16.0
22
NOVA PLUS Installation & Operation Manual -
POWER FLAME INCORPORATED
DC4 DRAFT CONTROL
ENTER
ESC
®
17. BURNER START UP INFORMATION & TEST DATA
The following information shall be recorded for each burner start up:
Power Flame Model No. _____________ Invoice No.__________________ Serial No.__________________________________
Installation Name_________________________________ Start Up Date____________________________________________
Start Up Contractors Name___________________________________ Phone________________________________________
Name of Technician Performing Start Up______________________________________________________________________
Type of Gas Natural
LP Other __________________________
Gas Firing
Gas Pressure at Train Inlet
Flame signal Readings
Stack Outlet Test Point Draft
Burner in Off Position ________” W.C.
Pilot________________________
Low Fire ____________________
Low Fire ____________________
High Fire____________________
Gas Pressure at Train Inlet
High Fire____________________
Low Fire_______________________
Net Stack Temperature
High Fire ______________________
O
2
Low Fire ____________________
Low Fire ____________________
High Fire____________________
Gas Pressure at Firing Head
High Fire____________________
Low Fire_______________________
Combustion Efficiency
High Fire ______________________
CO
Low Fire ___________________%
Low Fire ____________________
High Fire___________________%
Gas Pressure at Pilot Test Tee
High Fire____________________
______________________________
NOx Measured
Input Rate BTU/HR
Low Fire ____________________
Power Supply
Low Fire ____________________
High Fire____________________
Volts_____ Ph_______ Hz ________
High Fire____________________
Control Circuit Volts______________
Blower Motor amps at high fire _____
Over Fire Draft
______________________________
Low Fire ____________________
High Fire____________________
Control Settings
General
Gas
Operating control cut out setting_______
Low gas pressure switch_________in.
Operating control cut in setting________
High gas pressure switch_________in
Limit control cut out setting___________
Limit control cut in setting____________
Operation Checklist
Checked for Proper Operation of:
Yes
No
Yes
No
Low water cut off
( )
( )
Barometric damper
( )
( )
High water cut off
( )
( )
Boiler room combustion air and ventilation ( )
( )
Flame safeguard control ignition failure
( )
( )
provisions correct
Flame safeguard control main flame failure
( )
( )
Burner air flow switch
( )
( )
Induced draft fan controls
( )
( )
All gas lines checked for leaks
( )
( )
Over fire draft controls
( )
( )
Gas lines and controls properly vented
( )
( )
Fresh air damper end switch
( )
( )
Other system components (specify)
( )
( )
Notified_________________________________of the following system deficiencies:_______________________________________
___________________________________________________________________________________________________________
___________________________________________________________________________________________________________
___________________________________________________________________________________________________________