NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

1.

GENERAL PRODUCT INFORMATION

Principal of Operation

The Power Flame NOVA Plus™ Combustion System employs a patented, fully premixed,

surface stabilized combustion technology to provide proven ultra-low NOx solutions - Sub 9 to

12 PPM - for commercial, industrial, and process applications. Premixing fuel and air assures

complete combustion with minimal levels of CO and unburned hydrocarbons. The all metallic

firing head guarantees reliable and consistent performance at the operating conditions

necessary to provide single digit NOx emissions. The NOVA Plus is a simple, cost effective,

field proven system designed to meet today’s most stringent emissions requirements.

Power Flame provides a U.L. listed, factory tested package tailored to your job specific

requirements up to NVC10. The NOVA Plus is suitable for use on firetube and watertube boiler

applications, as well as process heaters. It will operate with uniform heat flux and excellent

flame stability over a broad range of operating conditions.

The modular concept that is the basis for all Power Flame burners keeps the initial investment

low and maintenance costs at a minimum across the life of the burner. The NOVA Plus is fitted

with a state of the art control system and integral panel.

Combustion air flow is controlled by a multi-louvered damper assembly. Combustion air is

supplied by an integral motor-driven blower, which discharges into the burner mixing spool

assembly. Gaseous fuel and air mix in the burner mixing spool. The premixed gaseous fuel

and air flow down the center plenum of the cylindrical element and through the metal material.

Ignition occurs on the outer surface.

The air-fuel ratio is established at the time of start-up and proven with combustion test

equipment to provide the lowest practical oxygen with a clean flame and single digit NOx

emissions.

A Flame Safeguard Controller programs the firing cycle. The operating cycle is sequenced to

ensure normal and safe conditions before fuel can be introduced into the combustion chamber

area. The complete firing cycle is supervised to ensure that ignition of main flame is properly

established and maintained. Flame monitoring is provided by an ultraviolet type scanner.

The limit circuit includes the operating limit control to maintain a set operating pressure or

temperature, as well as a high limit control to guard against excessive pressure or temperature.

Low water and other similar safety controls can be interlocked into the burner control system to

satisfy specific job and/or code requirements.

The control circuit is normally 120 volts. A control circuit transformer may be furnished to

provide the 120 volt control circuit for a polyphase motor application.

The pre-wired Control Panel is mounted and wired as an integral part of the burner in

accordance with recommendations of Underwriters Laboratories, Inc. and The National

Electrical Code. Components are wired to numbered terminal strips. Panel and burners are

factory fire tested before shipment. Comprehensive wiring and gas piping diagrams are

furnished with each burner in accordance with individual job or application requirements. Wall

mounted or free standing control panels are also available.

1

26

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

18.

 

OWNER OPERATING INSTRUCTIONS

FOR YOUR SAFETY

If you smell gas:
1.

Open windows

2.

Do not touch electrical switches

3.

Extinguish any open flame

4.

Call your gas supplier immediately

Do not store or use gasoline or other flammable liquids and vapors in the vicinity of this or any

other appliance.

IMPORTANT PRECAUTIONS

1.

Never attempt to light burner with

paper or other materials.

2.

Never experiment with the burner.

3.

Never change the fuel or air

adjustments without consulting with

the burner service company.

4.

Never attempt to light the burner if

combustion chamber contains any

unburned fuel or gases.

5.

Never throw waste paper, rags, garbage

or other waste materials into the

combustion chamber.

6.

Never wash out heating equipment room

without first covering the burner with

waterproof material.

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause injury or property

damage.  Refer to the burner manual.  For assistance or additional information consult a qualified

installer, service agency or the gas supplier.

Preparation for Start Up - All Fuels 

 

1.

Ensure that the system is in working order.

If heat exchanger is a boiler, ensure that

proper water level is available.

2.

Set the burner control panel switch to the

OFF position.

3.

Combination Gas Burner – set the fuel selector

switch to the fuel to be burned.

 

Start Up

1.

Manually open and close the main gas shut off

cock, leak test cock and pilot cock to determine

that they operate freely.  Open all three cocks.

(Reset low gas pressure switch if supplied).

2.

Set the main power switch and burner panel

control switch to the ON position.  Wait 30

seconds and turn up thermostat or operating

control to the desired setting.

3.

The burner blower motor will start and after

a suitable pre-purge period (this will vary with

the type of flame safeguard control supplied –

but will usually be a minimum of 30 seconds),

the burner pilot will light, after which the main

flame will be established.

4.

If the system does not respond properly,

contact your qualified burner service company.

EXTENDED SHUT DOWN

1.

Place main power switch and burner control panel switch in the OFF position.

2.

Close all gas valves.

3.

Cover burner to protect it from dust and dampness.

MAINTENANCE

1.

See Maintenance section in burner manual for suggestions on periodic maintenance and

Burner Service Company 

Date of Installation

Address 

Telephone

service.

4.

Turn the thermostat or operating control

down to its lowest setting.

5.

Check fuses and replace as necessary.

6.

Depress the flame safeguard programming

control reset button.

Remove this page and post near burner

.

Summary of Contents for Nova Plus

Page 1: ...Copyright 2006 Power Flame Incorporated Printed in U S A Power F 4 DRAFT CONTROL ENTER ESC Power Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual ...

Page 2: ...witches 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R...

Page 3: ...s 6 9 Burner Mounting General 6 10 Combustion Chamber General 7 11 General Start Up Procedures 8 12 Burner Start Up and Service Test Equipment Required 10 13 Burner Start Up Sequence Instructions 10 14 Gas Pilot Ignition Adjustment 15 15 Trouble Shooting Suggestions 16 16 Maintenance 19 17 Burner Startup Information Test Data 22 18 Owner Operating Instructions 26 NOVA PLUS Installation Operation M...

Page 4: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 5: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 6: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 7: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 8: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 9: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 10: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 11: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 12: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 13: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 14: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 15: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 16: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 17: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 18: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 19: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 20: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 21: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 22: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 23: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 24: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 25: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 26: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 27: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 28: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 29: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 30: ... 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R For us...

Page 31: ...er Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual Power Flame Incorporated 2001 South 21st Street Parsons KS 67357 Telephone 620 421 0480 FAX 620 421 0948 Product Support 620 820 8301 Website http www powerflame com e mail CSD powerflame com ...