5
Power-Flo Pumps & Systems • 877-24PUMPS • www.powerflopumps.com
PFEH
Submersible Effluent Pumps
Receiving Inspection
Upon receiving the pump, it should be
inspected for damage or shortages.
If damage has occurred, file a claim
immediately with the company that
delivered the pump. If the manual is
removed from the packaging, do not
lose or misplace.
Storage
Any product that is stored for a period
longer than six (6) months from the
date of purchase should be bench
tested prior to installation. A bench
test consists of, checking the impeller
to assure it is free turning and a run
test to assure the motor (and switch
if provided) operate properly. Do not
pump out of liquid.
Controls
Manual models require a separate
approved pump control device or panel
for automatic operation. Be sure the
electrical specification of the control
selected properly match the electrical
specifications of the pump.
Submergence
The pump should always be operated in
the submerged condition. The minimum
sump liquid level should never be less than
above the pump’s volute (See Figure 1).
Installation
There are two methods of installing
effluent pumps:
1.) In a Flex-Hose system, most commonly
used in interceptor tanks and.
2.) A slide rail in a package system or
concrete wet well, which allows the
pump(s) to be installed or removed
without requiring personnel to enter
the wet well.
The sump or basin shall be sealed
and vented in accordance with local
plumbing codes.
This pump is designed
to pump effluent or wastewater,
nonexplosive and noncorrosive liquids
and shall NOT be installed in locations
classified as hazardous in accordance
with the National Electrical Code (NEC)
ANSI/NFPA 70 or Canadian Electric
Code (CEC).
The pump should never be
installed in a trench, ditch, or hole with
a dirt bottom. The legs will sink into
the dirt and the suction will become
plugged.
The installation should be at a sufficient
depth to ensure that all plumbing is
below the frost line. If this is not feasible,
remove the check valve and size the
basin to accommodate the additional
backflow volume.
Discharge Piping
Discharge piping should be as short
as possible and sized no smaller than
the pump discharge.
Do not reduce
the discharge pipe size below that
which is provided on the pump.
Both
a check valve and a shut-off valve are
recommended for each pump. The
check valve is used to prevent backflow
into the sump. The shut-off valve is
used to manually stop system flow
during pump servicing.
Liquid Level Controls
The level control(s) should be mounted
on the discharge piping, a cable rack
or float pole. The level control should
have adequate clearance so it cannot
hang up in it’s swing and that the pump
is completely submerged when the
level control is in the “Off” mode. By
adjusting the cord tether the control
level can be changed. One cycle of
operation should be observed, so that any
potential problems can be corrected.
It is recommended that the level control
float should be set to insure that the liquid
in the sump never drops below the top of
the motor housing or a minimum level of
17 inches above the basin floor.
Electrical Connections
Power cable:
The power cable mounted to the pump
must not be modified in any way except
for shortening to a specific application.
Any splice between the pump and the
control panel must be made in
accordance with the electric codes. It is
recommended that a junction box, if used,
be mounted outside the sump or be of
at a minimum Nema 4 construction if
located within the wet well.
DO NOT USE
THE POWER CABLE TO LIFT PUMP.
Always rely upon a Certified Electrician
for installation.
Overload Protection:
Single Phase
- The stator in-winding
overload protector used is referred to as
an overheating protector and operates
on the combined effect of temperature
and current. This means that the
overload protector will trip out and shut
the pump off if the windings become too
hot, or the load current passing through
them becomes too high.
Receiving & Installation
Recommended
Submergence Level
Minimum
Submergence Level
Bottom of Feet
7”
Figure 1