background image

The system has been equipped with ¾” hex override couplers located on a drive
component of the system.  Due to the size and weight of some rooms, assistance may
be needed and care taken during the process.  Use the following steps to mechanically
operate the room:

1. Locate the motor and ¾” hex coupler.  

(Figure 8)

 The hex coupler may not be

attached to the motor as pictured but attached to a system drive component.

2. Unplug each motor connector.  Leave the sensor connector attached.
3. With your thumb, depress the spring lock lever on the right hand side of the boot

cover.  Then, rotate the override lever counter-clockwise with your index finger to
disengage the motor brake.

 (Figure 9)

4. Use a wrench or socket and ratchet to turn the override coupler in the direction

required to retract the room.

5. Once room is fully retracted, re-engage brake lever on motor (Figure 9).
6. Reconnect the motor leads to the connector.
7. Take the unit to an authorized dealer for service.  Do not use the slideout room as

damage to the room may result.

After the room has been 
moved in the desired direct- 
ion, the brake levers on each 
motor MUST be returned to 
the "engaged" position.  When 
the motor brake is 
disengaged the slideout room 
will not lock into place; 
therefore, the room will not be 
sealed.  When the room has 
been manually retracted, be 
sure to install the transit bars 
(if so equipped) and return the 
motor brake lever to its 
normal engaged position in 
order to seal and lock the 
room into position.  Do not 
travel unless each motor 
brake is in the "engaged" 
position!

If the room has been moved 
while the motor sensing 
control harness has been 
unplugged, do not attempt to 
use the room again until a 
service center has 
reprogrammed the 
computerized controller 
according to the service 
manuals instructions.  Failure 
to reset the controller may 
cause damage to the system 
or coach.

Page 6

Override Modes

WARNING

S

!

WARNING

S

!

CAUTION

S

!

„„„„B  !;    H!; „„„„

Your system can be manually overridden

.

During override mode the 
control has no stop 
locations.  Use another 
individual to assist in deter-
mining when the room is 
retracted.  Damage to the 
room can occur during over 
travel.

     NOTE:

€:H!B ; $B> ! B  !B
        not been moved for 45 seconds or if a fault is detected during overriding, the LED will 
B;H *'  BB ; <:*'
        seconds of flashing, the control will automatically default to fault code 1 (stops not 
        programmed) and the override mode must be re-done.
€zB  !   =; !!

Program Mode

) after the 

        system has been overridden.
1.

Emergency Retract Mode

 - use this procedure when there is NO loss of power or

electrical problem with the system.

1. Remove the touchpad (

Fig 7)

 from the wall

2. Press and hold the “Set Stops/Clear Fault” button on the back of the wall

touchpad for 5 seconds

  (Figure 4)

.  Both LED’s will light while the button is

held down. 

 (Figure 7)

     NOTE:

€:] $B`F=BBF!<
€B  !j;;B  ! "B  ! ">$B  !
         locks will retract automatically.

3. The unit is now ready to retract the room.

<B`=  B  B B;?(@B

room is fully retracted

4. Re-install the wall touchpad.
5. Take your unit to a certified dealer for repairs.  Done

2.

-or-

 

Emergency Retract Module (ERM)

 - This procedure is an alternate to the above

;  H=B   [`*]*''''*'†<?*=<
zB"[`*'*'''**&(@=;B ! <zB" !
    that will bypass the control and send power to the slideout motors.
3.

-or-

 

Manual Crank Mode

  -  use this procedure when the above procedures do not wor

k.

SENSOR

CONNECTOR

MANUAL OVERRIDE

¾” HEX COUPLER

BRAKE LEVER

UNDER BOOT

MOTOR 

CONNECTOR

Figure 8

Lock Lever

Brake Lever

Engage

Disengage

Figure 9

Summary of Contents for 1510000120

Page 1: ...stallation Installation Problems Program Mode Operation Mode Preventative Maintenance Fault Diagnostics Troubleshooting Override Modes Wiring Diagram 6 7 7 P N 81 1291 for proper installation of rail assemblies installation of room locks Control and touchpad Installation Refer to proper wiring diagram in back of manual B B nents from the elements and being hit but is easily accessible for service ...

Page 2: ...he control is also equipped to help troubleshoot the system during installation Count the number of LED flashes and refer to Fault Diagnostics section previous If you are still having difficulties programming the system and prior to replacing the control verify the system has been wired correctly and the in stop location was programmed before the out stop location was programmed CAUTION S WARNING ...

Page 3: ... motor rotation must be determined and programmed with the control Ref Step 2 Damage to the room or system may result Once control has been programmed correctly this step will not need to be repeated CAUTION S WARNING S Prior to extending or retracting the room take a moment to insure the following 1 Follow the coach manufacturer instructions regarding the leveling of the coach and room slide out ...

Page 4: ...cting the room take a moment to insure the following 1 Follow the coach manufacturer instructions regarding the leveling of the coach and room slide out operation 2 Verify the battery is fully charged Keeping the coach running will ensure proper voltage for room extension retraction 3 Park brake must be set 4 Check both inside and outside of the vehicle to make sure there are no people who could b...

Page 5: ...or Excessive Battery Voltage Bad battery Replace battery Battery Voltage is above 18 0V when room movement was initiated 5 Minor Slideout motor drawing Excessive system room drag Remove obstruction re adjust room reset excessive current obstruction improper stop stops or replace damaged locations or damaged component component 6 Major Slideout Motor Short Shorted wiring or motor Inspect motor harn...

Page 6: ...tor sensing control harness has been unplugged do not attempt to use the room again until a service center has reprogrammed the computerized controller according to the service manuals instructions Failure to reset the controller may cause damage to the system or coach Page 6 Override Modes WARNING S WARNING S CAUTION S B H Your system can be manually overridden During override mode the control ha...

Page 7: ...Page 7 Wiring Diagram Programmable Stop Control Wtih Room Locks Programmable Stop Control ...

Page 8: ...Page 8 Additional References located at www lci1 com 3010001346 Owners Manual Room Slideout System with Control Box 1510000120 and 1510000121 82 SO539 Encoder Test 1 82 SO540 Encoder Test 2 ...

Reviews: