SS3L / SS3R Series
www.powergenex.com
12
3.2.
Specifications for Fieldbus Communication
Specification
Foundation
TM
Fieldbus Version 2.0
Physical layer
Model 113,121 (IEC 61158-2)
Transmission rate
31.25 kbit/s
Supply voltage
Bus-powered : 9 ~ 32 VDC
Block types
2 AI Function Block
1 AO Function Block
2 DI Function Block
1 Transducer Block
1 Physical Block
Max. execution time
AO block: 31.25 milliseconds
Supply voltage
Power feed from the fieldbus: 9 ~ 32 VDC
Max. permissible voltage
36 VDC
Power consumption
16 mA
Certificate
FF Conformance Test ITK 6.1.1
Device name
PG-SS Positioner
Dev. ID
0003460001_PG-SS_XXXXXXXX
Unit address
Between 10 and 27, default address 247
Class
LM profile 32L, 31PS
Factory default
The PG-SS Positioner is not delivered in an aligned state. To
adjust the operating range and control parameters, an
automatic configuration must be run on the unit. Otherwise,
the transducer block remains in out-of-service mode.
Diagnostic functions
Self-diagnostics for the PG-SS Positioner hardware and
software, valve diagnostics with enhanced alarm handling