SS3L / SS3R Series
www.powergenex.com
32
11.3.
Parameters
11.3.1.
Main Parameters
Ref.
Parameter
Description
Function
Default
11.5.1
INPU
Input signal
4…20mA or 20…4mA
4…20mA
11.5.2
R / DA
RA / DA
Reverse acting or direct acting
RA
11.5.3
L / E.Q
Characteristic
Linear, E.Q. % (1:25 or 1:50),
Quick open or User set (17points)
Linear
11.5.4
SPAN
Span adjustment
0…100%
100%
11.5.5
ZERO
Zero adjustment
0…99%
0%
11.5.6
PID
P-GN / I-GN / D-GN
Auto-set
11.5.7
CTRL
Control paraeters
See 11.3.2 CTRL
ㆍ
11.5.8
DEAD
Signal dead band
0…9.99%
0%
11.5.11
SUB
Sub-Parameters
See 11.3.3 SUB
ㆍ
11.3.2.
CTRL - Parameters (speed control adjustment)
Ref.
Parameter
Description
Function
Default
11.5.7.A
SPED
Response speed
0…1000
1000
11.5.7.B
GAP
CONTROL GAP
AUTO
11.5.7.C
KISP
AUTO
11.5.7.D
GNLT
GAP LIMIT
AUTO
11.5.7.E
CNLT
CONTROL LIMIT
AUTO
11.5.7.F
HDGP
HARD / GRAPHITE
OFF
11.3.3.
SUB - Parameter
Ref.
Parameter
Description
Function
Default
11.5.9.A
SHUT
Shut-off
0…9.9%
0.3%
11.5.9.B
FOPN
Full-open
0…9.9%
0.3%
11.5.9.C
OUT
Output signal
4…20mA or 20…4mA
4…20mA
11.5.9.D
SPLT
Split range
4…12mA or 12…20mA
4…20mA
11.5.9.E
LCD
Change of display position
FOR / REV
FOR
11.5.9.F
ALAM
Alarm limit low, high
AL1L / AL1H, AL2L / AL2H
0…10%,
90…105%
11.5.9.G
ICAL
IN4M / IN20
sets the values in accordance with
4~20mA input signals
Factory
setting
11.5.9.H
FCAL
FB4M / FB20
sets the values in accordance with
4~20mA output signals
Factory
setting
11.5.9.I
POLL
HART polling address
0…15
0
11.5.9.J
PST
Partial stroke testing
checks a valve status
OFF
11.5.9.K
ADDR
PROFIBUS address
0…125
126
Note that the PST function (Partial Stroke Testing) is loaded at the factory on demand
only when requested.