SS3L / SS3R Series
www.powergenex.com
40
NOTES
1. This user setting has a linear characteristic as standard.
2. 5MA means % corresponding to 5mA.
3. Input all 4MA to 20MA for a required user set characteristic curve.
※ If Shut Off option is set, the set value at 4mA is maintained during interval of the Shut Off setting value as shown in Example 2).
The curve goes according the user set value after interval of the Shut Off setting value. (0.3% is the default value of Shut Off.)
As Shut-Off is set to 5% in Example 2), the curve maintains by 50% from 4 to 4.8mA and moves forward according to the user set.
11.5.4.
[SPAN] Span Adjustment (default: 100)
SPAN
100
0 - 100%
11.5.5.
[ZERO] Zero Adjustment (default: 0)
ZERO
0
0 - 99%
Zero can be adjusted to 0 – 99%.
① Be sure to supply 20mA input signal before adjusting SPAN.
② Push
DN button one time, Span will decrease by 0.1%. Keep pushing
DN
button, Span will decrease fast.
③ For a quick Span setting, push
DN button for 5 seconds. (see 10.2)