SS3L / SS3R Series
www.powergenex.com
43
11.5.7.E
[CNLT] – Control Limit (default: automatically-set)
CNLT
AUTO
50-1250
CNLT is to limit a control range and set
automatically during an auto-calibration process.
When 0% - 100% input signal is supplied, a
recognition range of the positioner is settled
according to CNLT.
If CNLT is increased as shown in Graph 3, a control
speed can become faster but a hunting problem
can happen. If CNLT is decreased as shown in Graph
4, a control speed can become slower but the
positioner works more stably.
CNTL can be adjusted by 100.
11.5.7.F
[HDGP] – In case of a hard packing friction (default: Off)
HDGP
OFF
ON
HDPG is helpful to eliminate a hunting problem with a hard packing friction.
11.5.8.
[DEAD] Setting of Dead Band (default: 0.5)
DEAD
0.5
0-9.99%
If there is a difference between Setting Value(SV) and Present Value(PV), adjust Dead Band to 0 - 9.99%.
0.5% is a standard factory setting. For reference, 0.50 corresponds to 0.5% and the
maximum value is 9.99 % (9.99).