[ICAL] – Setting of Input Signal (default: factory setting)
ICAL
IN4M
IN20
This is to match 4mA and 20mA input signals from a signal calibrator with the internal setting 0%
and 100% of the positioner and save onto memory.
If 4mA output signal is measured as 4.2mA and 20mA output signal as 19.8mA with a signal
calibrator on site, 4.2mA can be recognized as 0% and 19.8mA as 100% by re-setting with ICAL.
If ICAL is set at 4mA and 20mA, the middle output signals between 4mA and 20mA are
set automatically. See [11.5.3 L/EQ] if it is necessary to change other characteristic
curve.
11.5.9.H
[FCAL] – Setting of Output Signal (default: factory setting)
FCAL
FB4M
FB20
This is to re-set the 4 – 20mA output signals coming from the positioner.
The factory setting is that 4mA is sent at 0% and 20mA is sent at 100%.
<Setting of FB4M>