6 Stop Running, Dismantle, Discard Inverter
65
6.2 Dismantle the Inverter
After the connection among inverter and grid and PV string is completely disconnected and wait for
30min at least, ensure that the inner capacitor discharge completely, and then the inverter can be
dismantled.
Step 1
Disconnect all connection successively in reversed procedure of 3.6 Electrical Connection.
Step 2
Dismantle the inverter in reversed procedure of 3.5 Inverter Installation.
Step 3
If the inverter will be installed and used in the future, please dismantle the installation holder on the
wall or bracket, then package and store the inverter properly. (see 7.1 Package and 7.3 Storage).
----End
6.3 Discard the Inverter
For the inverter that certain not to be used, user needs to discard the inverter according to related
provision.
The battery, module and other components inside the inverter may pollute the environment, please do
corresponding dispose on the basis of related provision.