13
3-3. Audible Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Bypass Mode
Sounding every 10 seconds
3-4. LCD display wordings index
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
LLS
Low loss
HLS
High loss
TP
Temperature
CH
Charger
BF
Battery fault
FU
Bypass frequency unstable
EE
EEPROM error
3-5. UPS Setting
There are two parameters to set up the UPS.
Parameter 1: It’s for program alternatives.
Parameter 2: It’s the setting options or values
for each program.
01: Output voltage setting
Interface
Setting
For 200/208/220/230/240 VAC models, you may choose
the following output voltage:
200: presents output voltage is 200Vac
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac(Default)
240: presents output voltage is 240Vac
For 100/110/115/120/127 VAC models, you may choose
the following output voltage:
100: presents output voltage is 100Vac
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac(Default)
127: presents output voltage is 127Vac
Parameter 2
Parameter 1