4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

No indication and alarm even 
though the mains is normal.   

The AC input power is not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 

mains.   

The  AC  input  is  connected 
to the UPS output. 

Plug AC input power cord to 
AC input correctly.   

The icon 

  and 

 

 

flashing on LCD display and alarm 
is sounding every second. 

The external or internal 

battery is incorrectly 
connected. 

Check  if  all  batteries  are 

connected well. 

Fault code is shown as 27 and 
alarm is continuously sounding. 

Battery voltage is too  high 
or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and 

alarm is continuously sounding. 

Battery  voltage  is  too  low 

or the charger is fault. 

Contact your dealer. 

The icon 

  and 

  is 

flashing on LCD display and alarm 
is sounding twice every second. 

UPS is overload   

Remove  excess  loads  from 
UPS output. 

UPS is overloaded. Devices 
connected to the UPS are 

fed directly by the electrical 
network via the Bypass. 

Remove  excess  loads  from 
UPS output. 

After repetitive overloads, 
the UPS is locked in the 

Bypass mode. Connected 
devices are fed directly by 
the mains. 

Remove  excess  loads  from 
UPS output first. Then shut 

down  the  UPS  and  restart 
it. 

Fault code is shown as 43 and The 

icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

The UPS shut down 

automatically because of 
overload at the UPS output. 

Remove  excess  loads  from 

UPS output and restart it. 

Fault code is shown as 14 and the 
icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

The UPS shut down 
automatically because 
short circuit occurs on the 

UPS output. 

Check  output  wiring  and  if 
connected  devices  are  in 
short circuit status. 

Fault code is shown as 01, 02, 03, 
04, 11, 12, 13, 41 and 45 on LCD 
display and alarm is continuously 

sounding. 

A  UPS  internal  fault  has 
occurred.  There  are  two 
possible results: 

1. The load is still supplied, 
but directly from AC power 
via bypass.   
2.  The  load  is  no  longer 

supplied by power.   

Contact your dealer 

 

Summary of Contents for ERTN-1000

Page 1: ...GO 1000 GO 2000 GO 3000 ERTN 1000 ERTN 2000 ERTN 3000 Online UPS Uninterruptible Power Supply System Version 1 2 User Manual...

Page 2: ...n Only available for Rack UPS 5 2 3 Setup the UPS 6 2 4 Battery replacement Only for Rack UPS 8 2 5 Battery kit assembly Option for Rack UPS 9 3 Operations 11 3 1 Button operation 11 3 2 LCD Panel 11...

Page 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...it Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view GO 1000 GO 1000L IEC Type NEMA Type IEC Type GO 2000 GO 2000L...

Page 6: ...4 ERTN 1000 IEC Type For 110 120V For 220 230 240V ERTN 1000L ERTN 2000 IEC Type For 110 120V For 220 230 240V ERTN 2000L IEC Type...

Page 7: ...communication port 5 SNMP intelligent slot option 6 External battery connection only available for long run model 7 Output receptacles 8 Output circuit breaker 9 Output terminal 2 2 UPS Rack Installat...

Page 8: ...ker 40A between the mains and AC input of UPS in 3KVA 100 110 115 120127VAC models for safety operation c Upon completion of the wiring configuration please check whether the wires are securely affixe...

Page 9: ...ollow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower software icon and then choose your required O...

Page 10: ...tions and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the b...

Page 11: ...3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove adhesive tapes St...

Page 12: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step...

Page 13: ...rmal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message P...

Page 14: ...equency battery voltage load percent load in VA load in watts load current and ambient temperature K kilo W Watt V Volt A Amp VA Volt Amp percent Degree Hz Hertz Mode operation information Indicates t...

Page 15: ...alternatives Parameter 2 It s the setting options or values for each program 01 Output voltage setting Interface Setting For 200 208 220 230 240 VAC models you may choose the following output voltage...

Page 16: ...ng the low voltage point from 85Vac to 115Vac Default 85Vac 05 Acceptable high voltage setting in Bypass mode Interface Setting Press the Down key or Up key to set the acceptable high voltage point HL...

Page 17: ...ceptable low voltage setting in ECO mode Interface Setting Press the Down key or Up key to set acceptable low voltage point LLS in ECO mode For 200 208 220 230 240 VAC models the setting range is from...

Page 18: ...g mode Description LCD display Standby mode UPS is powered off and no output supply power but still can charge batteries Online mode When the input voltage is within acceptable range UPS will provide...

Page 19: ...ypass mode can be set by front panel Alarm is sounding every 10 second Fault mode When a fault has occurred the ERROR icon and the fault code will be displayed 3 7 Faults Reference Code Fault event Fa...

Page 20: ...not connected or Battery Replace Sounding every second Over Charge Sounding every second Over temperature Sounding every second Charger failure Sounding every second Battery fault Sounding every secon...

Page 21: ...cess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS output After repetitive overloads the U...

Page 22: ...battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer Storage Before storing charge the UPS 5 hours Store...

Page 23: ...Ratio 3 1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 89...

Page 24: ...e utility is normal Current Crest Ratio 3 1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure...

Reviews: