17
06: Acceptable low frequency for bypass mode
Interface
Setting
Parameter 2:
Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
07: Acceptable high frequency for bypass mode
Interface
Setting
Parameter 2:
Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
08: Bypass mode forbidden/allowed
Interface
Setting
Parameter 2:
Allow
or forbidden bypass mode
FBD:
Bypass not allowed. When selected, it’s not allowed for
running in Bypass mode under any situations.
OPN:
Bypass allowed. When selected, UPS will run at Bypass
mode depending on the setting of “
Manual Bypass
enable/disable
”
09: Manual bypass enable/disable
Interface
Setting
Parameter 2:
ENA
: Manual bypass enabled. When selected, bypass mode is
activated.
DIS:
Manual bypass disabled. When selected, automatic bypass
is acceptable, but manual bypass is not allowed.
*Manual bypass means users manually operate UPS in Bypass
mode. For example, pressing “OFF” button in AC mode to turn the
UPS into Bypass mode.
10: Battery backup time setting
Interface
Setting
Parameter 2:
001~999:
Set the maximum backup time from 1 min to 999 min.
UPS will shut down to protect battery after backup time arrives.
The default value is 990.
DIS:
Disable battery discharge protection and backup time will
depend on battery capacity.