background image

 

20

3-8. Operating Mode/Status Description 

LCD display   

Operating mode 

Description 

 

AC mode

 

When the input voltage is within 
acceptable range, UPS will 
provide pure and stable AC power 
to output. The UPS will also 
charge the battery at AC mode.

 

 

CVCF mode 

When input frequency is between 
46Hz and 64Hz, the UPS can be 
set at a constant output 
frequency, 50 Hz or 60 Hz. The 
UPS will still charge battery under 
this mode. 

 

Battery mode 

When the input voltage is beyond 
the acceptable range or power 
failure, UPS will backup power 
from battery and alarm will beep 
every 4 seconds. 

 

Battery Test 

When UPS is in AC mode or 
CVCF mode, press “Test” key for 
more than 2 seconds. Then, UPS 
will beep once and start “Battery 
Test”. This operation is used to 
check the battery status. 

 

Bypass mode

 

When input voltage is within 
acceptable range and bypass is 
enabled, turn off the UPS and it 
will enter Bypass mode. Alarm 
beeps every two minutes. 

 

Fault status 

When fault occurs in UPS, it will 
display fault icon and fault code in 
LCD panel. 

3-9. Fault Code 

Fault event 

Fault code 

Icon 

Fault event 

Fault code 

Icon 

Bus start failure 

01 

None 

Battery SCR short 
circuited 

21 None 

Bus over 

02 

None 

Inverter relay short 
circuited 

24 None 

Bus under 

03 

None 

Battery or Charger short 
circuited 

2A None 

Bus unbalance 

04 

None 

Parallel communication 
failure 

35 None 

Inverter soft start failure 

11 

None 

Parallel output current 
unbalance 

36 None 

High Inverter voltage 

12 

None 

Over temperature 

41 

None 

Low Inverter voltage   

13 

None 

CPU communication 
failure 

42 None 

Inverter output short 
circuited 

14 

 

Overload 43 

 

Negative power fault 

1A 

None 

 

Summary of Contents for KNIGHT ONLINE SERIES

Page 1: ...USER S MANUAL KNIGHT ONLINE SERIES UPS 220V 1000 L 2000 L 3000 L Uninterruptible Power Supply System...

Page 2: ...E UPS INSTALLATION 5 2 3 SOFTWARE INSTALLATION 7 3 OPERATIONS 8 3 1 LCD PANEL 8 3 2 BUTTON OPERATION 8 3 3 LED INDICATORS AND LCD PANEL 10 3 4 AUDIBLE ALARM 110 3 5 SINGLE UPS OEPRATION 131 3 6 LCD DI...

Page 3: ...em Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockpr...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...re use NOTE There are two different types of online UPS standard and long time models Please refer to the following model table Model Type Model Type 6K R 6K R L 10K R Standard 10K R L Long time 2 1 R...

Page 6: ...ordance with the local electric laws regulations and execute the following instructions by professional personnel 1 Make sure the mains wire and breakers in the building are in compliance with the sta...

Page 7: ...k cover back to the rear panel of the UPS Warning Only for standard model Make sure the UPS is not turned on before installation The UPS should not be turned on during wiring connection Do not try to...

Page 8: ...Wrong connection may cause permanent damage of the UPS Make sure the protective earth ground wiring is correct The current spec color position connection and conductance reliability of wire should be...

Page 9: ...n to return to last menu in setting menu Test Up Button Battery test Press and hold the button more than 2s to test the battery while in AC mode or CVCF mode converter mode UP key Press this button to...

Page 10: ...e frequency battery voltage load information and internal temperature V input output voltage battery voltage Hz frequency load level C temperature KW active power KVA apparent power A output current M...

Page 11: ...ote LED lighting LED faded When the UPS under bypass mode but no bypass output voltage exists Bypass LED will flicker 3 4 Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping o...

Page 12: ...en switch on the devices one by one the LCD panel will display total load level 2 If it is necessary to connect the inductive loads such as a printer the in rush current should be calculated carefully...

Page 13: ...through monitoring software 7 Turn off the UPS with utility power supply in AC mode 1 Turn off the inverter of the UPS by pressing OFF button for at least 0 5s and then the buzzer will beep once The...

Page 14: ...intenance bypass switch on the rear panel and turn the maintenance switch to BPS position first 3 Switch off the input breaker and switch off the battery breaker only available for long run model or d...

Page 15: ...or down key to select the displayed information 1 Output Voltage 2 Output Frequency 3 Input Voltage 4 Input Frequency 5 Battery Voltage 6 Load Level 7 Output Current 8 Output Apparent Power 9 Output A...

Page 16: ...eptable high frequency for bypass mode Y 08 Bypass mode forbidden allowed Y 09 Manual bypass mode enable disable Y 10 Battery backup time setting Y Y Y Y Y 11 Hot standby function enable disable Y Y Y...

Page 17: ...y mode when input frequency is not within 56 64 Hz 03 Output frequency setting Interface Setting Parameter 2 Output Frequency 50 0Hz output frequency is setting for 50 0Hz 60 0Hz output frequency is s...

Page 18: ...USER S MANUAL KNIGHT ONLINE SERIES UPS 220V 6000 L 10000 L Uninterruptible Power Supply System...

Page 19: ...ot allowed for running in Bypass mode under any situations OPN Bypass allowed When selected UPS will run at Bypass mode depending on the setting of Manual Bypass enable disable 09 Manual bypass enable...

Page 20: ...erface Setting Parameter 2 Voltage range is from 9 9V to 9 9V and the default value is 0V NOTE Before making voltage adjustment be sure to disconnect all batteries first to get the accurate charger vo...

Page 21: ...s 1 group These parameters are for the battery backup time calculation 17 Backup time calibration Interface Setting Parameter 2 Calibrate the displayed backup time by adjusting this multiplier factor...

Page 22: ...ry Test This operation is used to check the battery status Bypass mode When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps ev...

Page 23: ...in the end of life 1 Recharge the battery 2 Correct the battery number 3 Replace the battery Warning 09 Overload Remove excess loads from UPS output Warning 0A 1 Fan is blocked 2 Fan is in the end of...

Page 24: ...ppens again If the problem still persists please contact the dealer for repair 2 Contact the dealer for repair Fault 03 The internal converter fails so the DC bus voltage is too low Contact the dealer...

Page 25: ...There is some error in the parallel system Contact the dealer for repair Fault 41 The internal temperature is too high and reaches the fault level shutdown point 1 Maybe the environment is hot 2 Mayb...

Page 26: ...atteries must be replaced In this case please contact your dealer Storage Before storing charge the UPS at least 7 hours Store the UPS covered and upright in a cool dry location During storage recharg...

Page 27: ...ode and to 90 when the output voltage is adjusted to 208VAC If the UPS is installed or used in a place where the altitude is above than 1000m the output power must be derated one percent per 100m Prod...

Page 28: ...allation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 3 3 Operations 5 3 1 LCD Panel 5 3 2 Button Operation 5 3 3 Audible Alarm 7 3 4 LCD display wordings index 7 3 5 UPS Setting 7 3 6 Operatin...

Page 29: ...em Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockpr...

Page 30: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 31: ...for L model 7 Output receptacles 8 Output circuit breaker 9 Output terminal 2 2 Setup the UPS Step 1 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using...

Page 32: ...r PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card Whe...

Page 33: ...Up key Press this button to display previous selection in UPS setting mode Switch to UPS self test mode Press and hold ON Mute button for 5 seconds to enter UPS self testing while in AC mode ECO mode...

Page 34: ...e frequency battery voltage load information and internal temperature V input output voltage battery voltage Hz frequency load level C temperature KW active power KVA apparent power A output current M...

Page 35: ...ameters to set up the UPS Parameter 1 For program alternatives Parameter 2 Option setting or values for each program 01 Output voltage setting Interface Setting For 200 208 220 230 240 VAC models O P...

Page 36: ...from 85Vac to 115Vac Default 85Vac 05 Acceptable high voltage setting in Bypass mode Interface Setting Press Down key or Up key to set the acceptable high voltage point HLS in bypass mode For 200 208...

Page 37: ...ptable low voltage setting in ECO mode Interface Setting Press the Down key or Up key to set acceptable low voltage point LLS in ECO mode For 200 208 220 230 240 VAC models setting range is from 7V to...

Page 38: ...disabled Default 00 Exit setting 3 6 Operating Mode Description LCD display Operating mode Description Standby mode UPS power off and no output supply power but still can charge battery Online mode I...

Page 39: ...s mode can be set up by the front panel Alarm is sounding every 10 second Fault mode While a fault has occurred the ERROR icon and the fault code will be displayed 3 7 Faults Reference Code Fault even...

Page 40: ...not connected or Battery Replace Sounding every second Over Charge Sounding every second Over temperature Sounding every second Charger failure Sounding every second Battery fault Sounding every secon...

Page 41: ...mains Remove excess loads from UPS output first Then shut down the UPS then restart it Fault code is shown as 43 and The icon is lighting on LCD display and alarm is continuously sounding UPS shut dow...

Page 42: ...aler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatu...

Page 43: ...15 6 Specifications Derate capacity to 60 of capacity in Frequency converter mode and to 80 when the output voltage is adjusted to 208VAC...

Reviews: