10
11: Bypass enable/disable when UPS is off
Interface
Setting
ENA: Bypass mode is enabled when UPS is off
DIS: Bypass mode is disabled when UPS is off (Default)
12: Autonomy limitation setting
Interface
Setting
0-999: backup time setting in minutes from 0-999 for output
outlets under battery mode.
0: while setting as
「
0
」
, backup time will be on 10 seconds.
999: while setting as
「
999
」
, backup time setting will be
disabled. (Default)
00: Exit setting
3-6. Operating Mode Description
LCD display
Operating mode
Description
Standby mode
UPS power off and no output supply
power, but still can charge battery.
Online mode
Input voltage within an acceptable
range, UPS provide pure and stable
AC power to output, charge the
battery under online mode also.
ECO mode
Energy saving mode:
Input voltage within voltage
regulation range, UPS will bypass
voltage to output for energy saving.
Converter mode
Input frequency within 40Hz -70Hz,
UPS can be set at a constant output
frequency, 50Hz - 60Hz.
UPS still charge battery under this
mode.