3.7    Cold start:   

When the UPS is off and there is no utility power, use the cold start feature to apply power to 
the loads from UPS‘s battery. Press the ON/TEST button until the UPS beeps. 

3.8    Shutdown mode:   

In  shutdown  mode  the  UPS  stops  supplying  power  to  the  load,  waiting  for  return  of  utility 
power.  If  there  is  no  utility  power  present,  external  devices  (e.g.,  servers)  connected  to  the 
computer  interface  can  command  the  UPS  to  shut  down.  This  is  normally  done  to  preserve 
battery capacity after the graceful shutdown of protected servers. The UPS will scroll the front 
panel indicators sequentially in shutdown mode. 

3.9    Green mode:   

To enabling/disabling Green Mode, please press ON button 2 times to enable/disable green 
mode, then the buck&boost / overload&replace battery LED will blink 5 times. 

Attention:

 If Green Mode is enabled, when UPS is working under Backup mode, the UPS will 

automatically shut down after 4 minutes if the load level remains low.

 

Attention:

 The UPS is designed with memory module. (The UPS will automatically memorize 

Green Mode status when switched off. If no manual operation to enable or disable the Green 
Mode at the time when UPS is switched on, the Green Mode status would remain as it was 
previously.). Green Mode can be enabled or disabled via software. 

4.

 

A

LARM

 

4.1    “BACKUP” (slow alarm):   

When  the  UPS  is  working  under  “BACKUP”  mode,  the  UPS  would  emit  audible  alarm.  The 
alarm stops when the UPS is return to “LINE” mode operation. Anyone can stop the alarm by 
press the “ON” button during backup mode.   

Attention: 

The alarm of “BACKUP” is going to beep every four seconds. (Slow-speed beep). 

Attention:

 The UPS provides mute function for the warning. When the beeping sound occurs, 

press "ON" to stop it; and press "ON" again to regain the sound. 

4.2 

“LOW BATTERY” (rapid alarm):   

In the “BACKUP” mode, when the energy of battery becomes to lower level. (about 20%~30%) 
The UPS beeps rapidly until the UPS shuts down from battery exhaustion or returns to “LINE” 
mode operation. 

Attention: 

The alarm of the batteries caused by low voltage beeps every second. (Fast-speed 

beep). 

Attention:

  The  UPS  provides  mute  function  for  the  warning.  Please  press  the  “ON”  button 

three times in one second. 

 

 

 

 

Summary of Contents for 1000AP

Page 1: ...U P S Line Interactive Sine Wave 1000VA 3000VA USER S MANUAL...

Page 2: ...ore CAUTION Do not open or mutilate the battery released electrolyte is harmful to the skin and eyes CAUTION A battery can present a risk of electric shock and high short circuit current The following...

Page 3: ...le of contents 3 Save these instructions 4 1 Presentation 5 2 Installation 8 3 Operation 10 4 Alarm 11 5 Software and Interface Port 12 6 Maintenance and Storage 14 7 Battery and Battery Cabinet 14 Ap...

Page 4: ...it can provide immediately backup power from the batteries without any interruption Complete transference will be achieved within 4m seconds with no interruption Beside this when the utility power is...

Page 5: ...TTERY indicator The LED illuminates when the UPS s battery is no longer useful and must be replaced Note When replace battery disconnect the utility power then open the case and take notice of the bat...

Page 6: ...ttery capacity 1 1 10 OFF button Press the OFF button to turn off the UPS and the loads 1 2 Rear Panel 7 2 1 8 6 3 4 5 1000VA 1500VA 2000VA Load Indicator Light no 5 Light no 4 Light no 3 Light no 2 L...

Page 7: ...the connected loads exceed the protected receptacle s capacity The center plungers of the circuit breakers fuse extend when tripped 1 2 6 RS232 interface Provide both RS 232 and relay signal to suppo...

Page 8: ...ttery pack and the connector cable are compatible Note External battery connection is not necessary The UPS works properly without external battery pack connection CAUTION Use only factory supplied or...

Page 9: ...essories of Rack mounted types Please install the types of units according to the following illustration 2 9 Installation with accessories of Stack types Please install the types of units according to...

Page 10: ...erating 3 4 Self test Use the self test to verify both the operation of the UPS and the condition of the battery In normal utility power push the ON TEST button more than 1 second and UPS performs a s...

Page 11: ...with memory module The UPS will automatically memorize Green Mode status when switched off If no manual operation to enable or disable the Green Mode at the time when UPS is switched on the Green Mode...

Page 12: ...ur dealer for more information on computer OS compatible solutions 5 2 Interface Kits A series of interface kits is available for operation systems that provide UPS monitoring Each interface kit inclu...

Page 13: ...wn when a high RS 232 level is sustained on pin 3 for 0 36 seconds 5 4 5 Pin 2 is the RS 232 data output 5 4 6 Pin 3 is also RS 232 data input RxD NOTE 1 Switch rating 40V 0 25A non inductive 2 Pin 5...

Page 14: ...cted to the computer interface port to avoid unnecessary draining the battery 6 3 To extend the storage 6 3 1 During the environment where the ambient temperature is 15 to 30 5 to 86 charge the UPS s...

Page 15: ...ault Contact the dealer or service center for help Buzzer keeps beeping Overload Take off some load Utility Indicating light is shining There is an open circuit on UPS input protector Move the Input N...

Page 16: ...300Joules 2ms Short circuit UPS output cut off immediately or protected by input circuit breaker Tele communication RJ45 x2 EMI RFI filter 100kHz to 10MHz Fuse Yes Alarm Buzzer beeps under backup mod...

Reviews: