background image

 

15 

 

A

PPENDIX A 

T

ROUBLESHOOTING

 

 

Problems 

Possible Reasons 

Solutions 

UPS can't operate after 
pressing On/Off 
switches 
No lights on, no 
warning sounds 

Input power source mistake 

Check out the power source 

Non-fuse switch on the rear 

panel hasn't been opened 

Press the non-fuse switch to its "on" 

position 

Time of pressing the ON 

button is too short 

Keep pressing the ON button over 1 second 

Output short circuit or 

overload on UPS 

Turn off UPS, take off all load to make sure 

there are no problems on it or any internal 
short circuit. Keep pressing the ON button 
over 1 second 

Indicates no utility, and 
it warns every several 
seconds 

 

No power source input 

Check out the input power source 

Non-fuse switch on the rear 

panel hasn't been opened 

Press the Non-fuse switch to its "on" 
position 

Fault light is on, the 

buzzer keeps beeping 

Fault 

Contact the dealer or service center for 
help 

Buzzer keeps beeping 

Overload 

Take off some load 

Utility Indicating light is 
shining 

There is an open circuit on 
UPS input protector   

Move the Input Non-fuse switch back to its 
normal position, re-engage UPS 

The voltage of utility is 
exceeding UPS input range 

Save the digital data and shutdown the 
applying program to make sure utility is 
within UPS range 

Available time of the 

batteries is too short 

Batteries haven't been 
charged 
UPS overload 
Batteries are aged and can't 
be charged fully 

Keep UPS "ON" for over 3 hours to 
recharge the batteries. Check out the 
loading and take off any non-crucial load 
equipment 

The charger is out of order 

Contact the dealer or service center for 
help 

The battery’s light is 

flashing when the 
power of UPS is 
supplied by utility. 

The voltage of batteries is too 

low or the batteries haven't 
been connected 

Check out the batteries part of UPS, make 
sure they are well connected.    If there is 
any damage on battery packs, replace new 
ones ASAP 

 

Summary of Contents for 1000AP

Page 1: ...U P S Line Interactive Sine Wave 1000VA 3000VA USER S MANUAL...

Page 2: ...ore CAUTION Do not open or mutilate the battery released electrolyte is harmful to the skin and eyes CAUTION A battery can present a risk of electric shock and high short circuit current The following...

Page 3: ...le of contents 3 Save these instructions 4 1 Presentation 5 2 Installation 8 3 Operation 10 4 Alarm 11 5 Software and Interface Port 12 6 Maintenance and Storage 14 7 Battery and Battery Cabinet 14 Ap...

Page 4: ...it can provide immediately backup power from the batteries without any interruption Complete transference will be achieved within 4m seconds with no interruption Beside this when the utility power is...

Page 5: ...TTERY indicator The LED illuminates when the UPS s battery is no longer useful and must be replaced Note When replace battery disconnect the utility power then open the case and take notice of the bat...

Page 6: ...ttery capacity 1 1 10 OFF button Press the OFF button to turn off the UPS and the loads 1 2 Rear Panel 7 2 1 8 6 3 4 5 1000VA 1500VA 2000VA Load Indicator Light no 5 Light no 4 Light no 3 Light no 2 L...

Page 7: ...the connected loads exceed the protected receptacle s capacity The center plungers of the circuit breakers fuse extend when tripped 1 2 6 RS232 interface Provide both RS 232 and relay signal to suppo...

Page 8: ...ttery pack and the connector cable are compatible Note External battery connection is not necessary The UPS works properly without external battery pack connection CAUTION Use only factory supplied or...

Page 9: ...essories of Rack mounted types Please install the types of units according to the following illustration 2 9 Installation with accessories of Stack types Please install the types of units according to...

Page 10: ...erating 3 4 Self test Use the self test to verify both the operation of the UPS and the condition of the battery In normal utility power push the ON TEST button more than 1 second and UPS performs a s...

Page 11: ...with memory module The UPS will automatically memorize Green Mode status when switched off If no manual operation to enable or disable the Green Mode at the time when UPS is switched on the Green Mode...

Page 12: ...ur dealer for more information on computer OS compatible solutions 5 2 Interface Kits A series of interface kits is available for operation systems that provide UPS monitoring Each interface kit inclu...

Page 13: ...wn when a high RS 232 level is sustained on pin 3 for 0 36 seconds 5 4 5 Pin 2 is the RS 232 data output 5 4 6 Pin 3 is also RS 232 data input RxD NOTE 1 Switch rating 40V 0 25A non inductive 2 Pin 5...

Page 14: ...cted to the computer interface port to avoid unnecessary draining the battery 6 3 To extend the storage 6 3 1 During the environment where the ambient temperature is 15 to 30 5 to 86 charge the UPS s...

Page 15: ...ault Contact the dealer or service center for help Buzzer keeps beeping Overload Take off some load Utility Indicating light is shining There is an open circuit on UPS input protector Move the Input N...

Page 16: ...300Joules 2ms Short circuit UPS output cut off immediately or protected by input circuit breaker Tele communication RJ45 x2 EMI RFI filter 100kHz to 10MHz Fuse Yes Alarm Buzzer beeps under backup mod...

Reviews: