5K VA – 12K VA UPS 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User’s and Installation Manual

 

I

EMC Statements 

CISPR 22 

NOTICE: 

Pursuant to CISPR 22 rules, this product has been tested and thereby complies to 

the conditions of a Class A digital device, which have been established for offering 
sufficient protection against dangerous interference for installation in a residential area. 
Installation and use of the equipment should comply with the instructions provided in order 
to avoid such interference due to the amount of radio frequency energy that is radiated and 
generated by the equipment. In spite of this, we cannot assure that a certain amount of 
interference may not occur in some installations. If, by turning on and off, it can be deduced 
that your radio or television reception is found to be influenced by harmful interference 
from the equipment, it is recommended to use one of the following preventive measures: 

 

Place the receiving antenna in a separate location or orientation. 

 

Ensure a greater distance is achieved between the receiver and the equipment. 

 

Ensure that your equipment is connected to an outlet on a separate circuit than the 
receiver. 

 

Contact a technician experienced with radio and TV or a dealer for further assistance. 

Declaration of Conformity Request 

Units labeled with a CE mark comply with the following standards and directives: 

 

Harmonic Standards: EN 50091-1-1 and EN 50091-2 

 

EU Directives:73/23/EEC, Council Directive on equipment designed for use within 
certain voltage limits 

93/68/EEC, Amending Directive 73/23/EEC 

89/336/EEC, Council Directive relating to electromagnetic compatibility 

92/31/EEC, Amending Directive 89/336/EEC relating to EMC 

The EC Declaration of Conformity is available upon request for products with a CE 
mark.

Summary of Contents for 12K VA

Page 1: ...fluenced by harmful interference from the equipment it is recommended to use one of the following preventive measures Place the receiving antenna in a separate location or orientation Ensure a greater...

Page 2: ...servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not isolated from AC input hazardous voltage may exist between battery terminals...

Page 3: ...nstallation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation and regulations Only qualified personnel should conduct these insta...

Page 4: ...management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of normal mode operation a battery discharge test is performed...

Page 5: ...in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operator 5 4 Storage 4 1 Storage Please adhere to the followi...

Page 6: ...ptions Avoid extremes of temperature and humidity Maximal battery life can be attained with a recommended temperature range of 15 C to 25 C Provide protection for the equipment from moisture Space and...

Page 7: ...8 5K 6KVA Rear panel With ISO 9 8K 12KVA Rear panel Without ISO...

Page 8: ...the installation site has all electrical connections properly carried out In addition refer to figures 2 and 3 to check the fuse and cable dimensions Isolate and secure the source against reclosing Bo...

Page 9: ...ters to select Default settings are as follows Settings Selection Factory default Output Voltage Setting 208 220 230 240 Vac 230V FOR HV series Input Bypass Voltage 10 10 15 15 20 10 15 Input Frequenc...

Page 10: ...RI Output 8 24 VDC Power Fig 5 Caution Max rated values 24Vdc 50mA 15 USB port option Connecting the UPS to your computer is accomplished through the USB port on the back of your computer USB complian...

Page 11: ...Push the ENTER button to confirm and enable your function f If no pressing within 10 seconds it will return to original status 4 ENTER button Use this button to enter enable or confirm the function t...

Page 12: ...CPU Version 19 UPS configurations 1 Various settings that have been chosen are shown in the UPS setting display 2 To enter configuration mode press the FUNC button for one second The first configurati...

Page 13: ...ed For UPS to predict Backup time 0 only internal batteries 1 one external cabinet 2 two external cabinets 0 Site wiring alarm Sit Fault Set You can enable or disable the site wiring alarm Enable Disa...

Page 14: ...ps The UPS is doing a battery test No action needed The UPS will return to normal operation when it successfully completes the battery test Over Charge Constant beep Batteries are overcharged Turn off...

Page 15: ...al and workmanship for a period of 24 months from its original date of purchase 25 10 Technical Specifications GENERAL Rated power 5000VA 6000 VA 8000 VA 10000 VA 12000VA at p f 0 7 Technology On line...

Page 16: ...mber of batteries 20 20 20 20 40 Backup time full load 7 min 6 min 5 min 6 min 6min Recharge time 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 Without ISOTR 280x580x570 280x58...

Page 17: ...28 MAINTENANCE SWITCH NORMAL BY PASS 1 2 INV MAIN INV MAIN or...