6.  Computer and alarm connections 

At the back of the UPS is an interface allowing direct communication with your computer 
system, the location of which can be found in figure 4. There is a RS232 serial data 
interface, one USB data interface and an emergency power off switch supplied. However, 
the RS232 port cannot be used when the USB interface is in use. 

In addition there is an optional interface slot that allows you to install different 
communications cards. It can be used parallel with either the RS232 or USB ports. 

Currently there are two cards available for the optional interface slot. An SNMP/WEB card 
allows management and monitoring over a network or internet, and the AS/400 card allows 
voltage free relay contacts. Your local dealer will have more information about these option 
cards. 

Connecting the UPS to a Computer 

The communication device for the UPS and PC comes as a complete package with power 
management software. Only the communication cable provided with UPS may be used to 
connect to your computer, which is accomplished through the UPS RS232 port. Also ensure 
that the operating system on your computer is supported. Instructions provided in the power 
management software will help with this installation. 

Other advanced power protection solutions such as SNMP are provided by your dealer. 

RS-232 Standard Interface port 

The RS-232 interface uses a 9-pin female D-sub connector. This information consists of 
data about utility, load and the UPS. The interface port pins and their functions are 
identified in the following table. 

 

 

 

Pin # 

Signal name

Direction (re UPS) 

Functions 

2 TxD  Output 

TxD 

Output 

RxD 

Input 

RxD / Inverter Off Input 

5 Common 

 

Common 

CTS 

Output 

Ac Fail Output 

DCD 

Output 

Low Battery Output 

RI 

Output 

+8-24 VDC Power 

 

Fig.5

 

Caution! Max rated values 24Vdc/50mA

 

15

USB port (option) 

Connecting the UPS to your computer is accomplished through the USB port on the back of 
your computer. USB compliant hardware and operating system will be necessary including 
installation of a UPS driver. The serial port cannot be used when using the USB port. The 
USB cable is standard and can be bought separately. 

6.1 EPO port (emergency power off) 

A customer-supplied switch located remotely can be used to open the EPO connection and 
allows UPS output receptacles to be switched off. Since the EPO shuts down the equipment 
immediately, orderly shutdown procedures are not followed and not by any power 
management software. The UPS will have to be manually restarted in order to regain power 
to the outlets. 

 

7.  User’s guide to operations 

Necessary information for operation of the unit is covered in this chapter. 

Normally the UPS runs automatically, but on those few occasions such as just 
after installation, all the starting and shutting down procedures are described 
herein. 

7.1 Starting and shutting down the UPS 

Starting the UPS 

 

Ensure that installation was correct and successful and that the input power cable is 
connected to a well-grounded outlet. 

 

The UPS can be started by pushing the “ON/OFF” button on the front panel. 

 

The UPS should now start its inspection of: internal functions, main synchronization 
and inverter startup. Then power should start to be supplied via the terminal block. 

 

During this inspection, the LCD will display “Ready on”. The LED shall light up when 
output power has commenced and the LCD will display “Line mode”. 

 

Switch on the loads. 

Shutting down the UPS 

 

Shut down and turn off the loads. 

 

Push the “ON/OFF” button on the front panel for two seconds. The alarm will sound 
and the UPS will shut down. 

 

The LCD will display UPS OFF for a few seconds. 

 

In emergency situations, the EPO located on the back of the unit should be used. 

Summary of Contents for 12K VA

Page 1: ...fluenced by harmful interference from the equipment it is recommended to use one of the following preventive measures Place the receiving antenna in a separate location or orientation Ensure a greater...

Page 2: ...servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not isolated from AC input hazardous voltage may exist between battery terminals...

Page 3: ...nstallation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation and regulations Only qualified personnel should conduct these insta...

Page 4: ...management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of normal mode operation a battery discharge test is performed...

Page 5: ...in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operator 5 4 Storage 4 1 Storage Please adhere to the followi...

Page 6: ...ptions Avoid extremes of temperature and humidity Maximal battery life can be attained with a recommended temperature range of 15 C to 25 C Provide protection for the equipment from moisture Space and...

Page 7: ...8 5K 6KVA Rear panel With ISO 9 8K 12KVA Rear panel Without ISO...

Page 8: ...the installation site has all electrical connections properly carried out In addition refer to figures 2 and 3 to check the fuse and cable dimensions Isolate and secure the source against reclosing Bo...

Page 9: ...ters to select Default settings are as follows Settings Selection Factory default Output Voltage Setting 208 220 230 240 Vac 230V FOR HV series Input Bypass Voltage 10 10 15 15 20 10 15 Input Frequenc...

Page 10: ...RI Output 8 24 VDC Power Fig 5 Caution Max rated values 24Vdc 50mA 15 USB port option Connecting the UPS to your computer is accomplished through the USB port on the back of your computer USB complian...

Page 11: ...Push the ENTER button to confirm and enable your function f If no pressing within 10 seconds it will return to original status 4 ENTER button Use this button to enter enable or confirm the function t...

Page 12: ...CPU Version 19 UPS configurations 1 Various settings that have been chosen are shown in the UPS setting display 2 To enter configuration mode press the FUNC button for one second The first configurati...

Page 13: ...ed For UPS to predict Backup time 0 only internal batteries 1 one external cabinet 2 two external cabinets 0 Site wiring alarm Sit Fault Set You can enable or disable the site wiring alarm Enable Disa...

Page 14: ...ps The UPS is doing a battery test No action needed The UPS will return to normal operation when it successfully completes the battery test Over Charge Constant beep Batteries are overcharged Turn off...

Page 15: ...al and workmanship for a period of 24 months from its original date of purchase 25 10 Technical Specifications GENERAL Rated power 5000VA 6000 VA 8000 VA 10000 VA 12000VA at p f 0 7 Technology On line...

Page 16: ...mber of batteries 20 20 20 20 40 Backup time full load 7 min 6 min 5 min 6 min 6min Recharge time 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 Without ISOTR 280x580x570 280x58...

Page 17: ...28 MAINTENANCE SWITCH NORMAL BY PASS 1 2 INV MAIN INV MAIN or...

Reviews: