background image

 

IV

The instructions contained within this safety manual are deemed important and 

should be closely followed at all times during installation and follow-up 

maintenance of the UPS and batteries. 

 

CAUTION 

The unit has a dangerous amount of voltage. If the UPS indicator is on, the unit’s 
outlets may have a dangerous amount of voltage even when not plugged into the 
wall outlet because the battery may continue to supply power. 

Care should be taken to undertake installation indoors free from 
electrically-conductive particles which is under temperature and humidity control 
in order to reduce the risk of electric shock. 

It is best to disconnect the device using the power supply cord. Ensure that the 
equipment is placed in a position near the outlet where easily accessible. 

Except replacing the batteries, all servicing on this equipment must be carried out 
by qualified service personnel. 

Before conducting any maintenance, repair or shipment, first ensure that 
everything is turned off completely and disconnected.

 

For additional safety instructions, please use the Safety Manual as reference. 

Special Symbols 

The following symbols used on the UPS warn you of precautions: 

RISK OF ELECTRIC SHOCK – Please observe the warning that a risk of electric 
shock is present. 

CAUTION: REFER TO OPERATOR’S MANUAL - Refer to the operator’s 
manual for additional information, such as important operating and maintenance 
instructions. 

SAFE GROUNDING TERMINAL - Indicates primary safe ground   

 

LOAD ON/OFF - Pressing this button turns on/off the output receptacles and the 
Indicator light. 

Please do not discard the UPS or UPS batteries as the UPS may have valve 
regulated, lead–acid batteries. Please recycle batteries.

 

 

1

1. Introduction 

The information provided in this manual covers single phase 5000 – 12000 VA, 
uninterruptible power systems, their basic functions, operating procedures, and emergency 
situations, also including information on how to ship, store, handle and install the 
equipment. Only detailed requirements of the UPS units are described herein, and 
installation must be carried out in accordance with this manual. Electrical installations must 
also carefully follow local legislation and regulations. Only qualified personnel should 
conduct these installations as failure to acknowledge electrical hazards could prove to be 
fatal. 

2. System description 

Several different kinds of sensitive electrical equipment stay protected by a UPS 
(Uninterruptible Power System) including computers, workstations, process control systems, 
telecommunications systems, sales terminals, other critical instrumentation, etc. The 
purpose of the UPS is to protect these systems from poor quality utility power, complete 
loss of power, or other associated problems. 

Electrical interference abounds in many forms causing problems in AC power, from 
lightning, power company accidents and radio transmissions to motors, air conditioners, and 
vending machines, among others. So protection of sensitive electrical equipment is vital to 
protect against power outages, low or high voltage, slow voltage fluctuations, frequency 
variations, differential and common-mode noises, transients, etc. 

In order to prevent power line problems reaching critical systems causing damage to 
software, hardware and causing equipment to malfunction, the UPS helps by maintaining 
constant voltage, isolating critical load output if needed, and cleaning the utility AC power. 

2.1 General description 

As a double conversion on-line UPS, it is able to supply uninterrupted, clean single-phase 
power to your critical systems while keeping batteries charged continuously, regardless of 
whether utility power fails or not. 

In event that a power failure lasts longer than a UPS backup time, it will shut down 
avoiding battery discharge, and as soon as voltage comes back, the UPS will automatically 
charge up and start recharging the batteries. 

As shown in fig.1 block diagram: 

 

An input filter reduces transients on the mains 

 

For maintaining full battery charge, AC-power is rectified and regulated in the rectifier 
feeding power to the inverter and battery converter. 

 

DC power is converted to AC in the inverter passing it on to the load. 

 

Power is maintained from the battery during a power failure. 

 

The converter increases voltage appropriately for the inverter. 

Summary of Contents for 12K VA

Page 1: ...fluenced by harmful interference from the equipment it is recommended to use one of the following preventive measures Place the receiving antenna in a separate location or orientation Ensure a greater...

Page 2: ...servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not isolated from AC input hazardous voltage may exist between battery terminals...

Page 3: ...nstallation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation and regulations Only qualified personnel should conduct these insta...

Page 4: ...management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of normal mode operation a battery discharge test is performed...

Page 5: ...in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operator 5 4 Storage 4 1 Storage Please adhere to the followi...

Page 6: ...ptions Avoid extremes of temperature and humidity Maximal battery life can be attained with a recommended temperature range of 15 C to 25 C Provide protection for the equipment from moisture Space and...

Page 7: ...8 5K 6KVA Rear panel With ISO 9 8K 12KVA Rear panel Without ISO...

Page 8: ...the installation site has all electrical connections properly carried out In addition refer to figures 2 and 3 to check the fuse and cable dimensions Isolate and secure the source against reclosing Bo...

Page 9: ...ters to select Default settings are as follows Settings Selection Factory default Output Voltage Setting 208 220 230 240 Vac 230V FOR HV series Input Bypass Voltage 10 10 15 15 20 10 15 Input Frequenc...

Page 10: ...RI Output 8 24 VDC Power Fig 5 Caution Max rated values 24Vdc 50mA 15 USB port option Connecting the UPS to your computer is accomplished through the USB port on the back of your computer USB complian...

Page 11: ...Push the ENTER button to confirm and enable your function f If no pressing within 10 seconds it will return to original status 4 ENTER button Use this button to enter enable or confirm the function t...

Page 12: ...CPU Version 19 UPS configurations 1 Various settings that have been chosen are shown in the UPS setting display 2 To enter configuration mode press the FUNC button for one second The first configurati...

Page 13: ...ed For UPS to predict Backup time 0 only internal batteries 1 one external cabinet 2 two external cabinets 0 Site wiring alarm Sit Fault Set You can enable or disable the site wiring alarm Enable Disa...

Page 14: ...ps The UPS is doing a battery test No action needed The UPS will return to normal operation when it successfully completes the battery test Over Charge Constant beep Batteries are overcharged Turn off...

Page 15: ...al and workmanship for a period of 24 months from its original date of purchase 25 10 Technical Specifications GENERAL Rated power 5000VA 6000 VA 8000 VA 10000 VA 12000VA at p f 0 7 Technology On line...

Page 16: ...mber of batteries 20 20 20 20 40 Backup time full load 7 min 6 min 5 min 6 min 6min Recharge time 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 Without ISOTR 280x580x570 280x58...

Page 17: ...28 MAINTENANCE SWITCH NORMAL BY PASS 1 2 INV MAIN INV MAIN or...