background image

 

 
 
 
 
 
 
 

 

 

Fig.1.

 Block diagram 

Efficiency Optimizer function 

The Efficiency Optimizer function is a new feature for the UPS adding cost effectiveness, 
minimizing power loss and reducing power consumption. Alternating between bypass and 
on-line modes is achieved automatically and in accordance with the conditions of the utility 
power. On-line mode may be used during times of intermittent power supply, and bypass 
mode when power flows smoothly in order to obtain greatest efficiency. Irregularities can 
be detected in less than a second, and on-line mode reactivated immediately. Switching 
back to online mode occurs when input voltage is outside ±10% or nominal (±15% 
selectable), when input frequency is outside of ±3Hz or when no input line is available. 

Although high efficiency is standard, the default operation is in on-line mode. Bypass can 
be activated in the LCD panel, though on-line can be run permanently if preferred. 

Free Run Mode 

The UPS operates in free run mode when input frequency is outside of the selected input 
frequency range. Free run mode is when output frequency does not match input frequency. 
When starting the UPS, the frequency regulation detected is 50 or 60 Hz ±0.25Hz. Please 
refer to chapter 7.2 if you want bypass available while running in free run mode. 

Diagnostic tests 

When you start the UPS, a diagnostic test is automatically executed that checks electronics, 
battery, and reports any problems on the LCD display. 

An advanced battery management system always monitors the conditions of the batteries 
sends any forewarnings if replacement is needed. Otherwise every 30 days of normal mode 
operation, a battery discharge test is performed and any problems reported on the LCD 
display. 

Except during the first 24 hours after startup while the UPS is in charging mode (please see 
chapter 7.2), diagnostic tests can be performed manually from the front panel at any time. 

Filter

By-pass

switch

Filter

Charger &

Battery

switch

Battery

Monitoring

panel

RS232 or

USB

Slot

Control

&

Monitoring

PFC&Booster

Inverter

 

3

2.2 System configuration 

The UPS device and the internal backup battery make up the system. Depending on the site 
and load requirements of the installation, certain additional options are available as a 
tailored solution. 

Planning a UPS system, the following should be taken into consideration: 

 

The total demand of the protected system shall dictate the output power rating (VA). 
Allow a margin for future expansion or calculation inaccuracies from measuring power 
requirements. 

 

Backup time needed will indicate the battery size needed. If load is less than the UPS 
nominal power rating then actual backup time is longer. 

 

The following options are available: 

 

External Battery Cabinets 

 

Transformer cabinets 

 

Maintenance bypass switches 

 

Connectivity options (relay card, SNMP/WEB card) 

The following UPS models are available 

Model 

Backup time 
Internal batteries 

Recharge time to 90% capacity 

UPS 5000VA 

  7min 

8 hours 

UPS 6000VA 

  6min 

8 hours 

UPS 8000VA 

  5min 

8 hours 

UPS 10000VA 

  6min 

8 hours 

UPS 12000VA 

  6min 

8 hours 

Additional External Battery Cabinets are available if more back-up time is needed. 

 

Summary of Contents for 12K VA

Page 1: ...fluenced by harmful interference from the equipment it is recommended to use one of the following preventive measures Place the receiving antenna in a separate location or orientation Ensure a greater...

Page 2: ...servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not isolated from AC input hazardous voltage may exist between battery terminals...

Page 3: ...nstallation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation and regulations Only qualified personnel should conduct these insta...

Page 4: ...management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of normal mode operation a battery discharge test is performed...

Page 5: ...in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operator 5 4 Storage 4 1 Storage Please adhere to the followi...

Page 6: ...ptions Avoid extremes of temperature and humidity Maximal battery life can be attained with a recommended temperature range of 15 C to 25 C Provide protection for the equipment from moisture Space and...

Page 7: ...8 5K 6KVA Rear panel With ISO 9 8K 12KVA Rear panel Without ISO...

Page 8: ...the installation site has all electrical connections properly carried out In addition refer to figures 2 and 3 to check the fuse and cable dimensions Isolate and secure the source against reclosing Bo...

Page 9: ...ters to select Default settings are as follows Settings Selection Factory default Output Voltage Setting 208 220 230 240 Vac 230V FOR HV series Input Bypass Voltage 10 10 15 15 20 10 15 Input Frequenc...

Page 10: ...RI Output 8 24 VDC Power Fig 5 Caution Max rated values 24Vdc 50mA 15 USB port option Connecting the UPS to your computer is accomplished through the USB port on the back of your computer USB complian...

Page 11: ...Push the ENTER button to confirm and enable your function f If no pressing within 10 seconds it will return to original status 4 ENTER button Use this button to enter enable or confirm the function t...

Page 12: ...CPU Version 19 UPS configurations 1 Various settings that have been chosen are shown in the UPS setting display 2 To enter configuration mode press the FUNC button for one second The first configurati...

Page 13: ...ed For UPS to predict Backup time 0 only internal batteries 1 one external cabinet 2 two external cabinets 0 Site wiring alarm Sit Fault Set You can enable or disable the site wiring alarm Enable Disa...

Page 14: ...ps The UPS is doing a battery test No action needed The UPS will return to normal operation when it successfully completes the battery test Over Charge Constant beep Batteries are overcharged Turn off...

Page 15: ...al and workmanship for a period of 24 months from its original date of purchase 25 10 Technical Specifications GENERAL Rated power 5000VA 6000 VA 8000 VA 10000 VA 12000VA at p f 0 7 Technology On line...

Page 16: ...mber of batteries 20 20 20 20 40 Backup time full load 7 min 6 min 5 min 6 min 6min Recharge time 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 Without ISOTR 280x580x570 280x58...

Page 17: ...28 MAINTENANCE SWITCH NORMAL BY PASS 1 2 INV MAIN INV MAIN or...

Reviews: