Only qualified specialists or technicians who conform to applicable safety standards may 

carry out the installation of this equipment. The installation must further comply with all 

local legislation and regulations. 
Follow all installation and safety instructions very carefully, otherwise those performing 

installation may suffer from a hazardous situation and the UPS or load connections may 

also be damaged. 

The high voltage and current contained within the UPS equipment can injure or 
kill personnel and damage equipment. 

 

For electrical installation, closely observe the nominal current rating of the source. 

Installing External battery cabinets 

 

First disconnect the UPS from mains and loads before attempting an External Battery 
Cabinet installation. 

 

Use the battery cable provided with the External Battery Cabinet to connect the External 
Battery Cabinet to the UPS. Connect a second battery cabinet to the first one with the 
cable provided if more than one is to be installed. 

 

Be aware of UPS parameters and changing the Battery pack quantity when using the 
external battery cabinets (see chapter 7.2) 

Installing UPS 

 

Ensure that the installation site has all electrical connections properly carried out. In 
addition, refer to figures 2 and 3 to check the fuse and cable dimensions. 

 

Isolate and secure the source against reclosing. Both input and output circuit breakers 
(located in the back) must be “OFF”. 

 

Refer to figure 2 for single cable input and figure 3 for dual cable input. Connect the 
UPS according to these diagrams. If installing dual cables, the interconnection jumper 
(b*) needs to be removed as in figure 2. Fuse and cable sizes are given in figure 3. 

 

During installation, if it cannot be determined that neutral is grounded or the 

identification of the neutral status of the mains supply is unreliable, an additional two 
pole disconnect device is necessary in the building installation. 

 

At the back of the unit you will find the Emergency Power Off (EPO), which when 
open will immediately shut down the logic circuit output of the UPS as in figure 2 and 3. 
Wiring the EPO signal is optional. 

 

Caution! 

Local safety requirements may require a separate external Emergency Power 

Off that opens output circuit breakers, and if so, use figures 2 and 3 for proper 
installation. Refer to local wiring rules. 

 

Should computer or alarm connections be used, use connections according to chapter 6 

of the manual provided with that option. The connections can be referred to on the rear 
panel. 

 

The installation is now complete. 

b*) removable jumper when dual input used 

Summary of Contents for 12K VA

Page 1: ...fluenced by harmful interference from the equipment it is recommended to use one of the following preventive measures Place the receiving antenna in a separate location or orientation Ensure a greater...

Page 2: ...servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not isolated from AC input hazardous voltage may exist between battery terminals...

Page 3: ...nstallation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation and regulations Only qualified personnel should conduct these insta...

Page 4: ...management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of normal mode operation a battery discharge test is performed...

Page 5: ...in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operator 5 4 Storage 4 1 Storage Please adhere to the followi...

Page 6: ...ptions Avoid extremes of temperature and humidity Maximal battery life can be attained with a recommended temperature range of 15 C to 25 C Provide protection for the equipment from moisture Space and...

Page 7: ...8 5K 6KVA Rear panel With ISO 9 8K 12KVA Rear panel Without ISO...

Page 8: ...the installation site has all electrical connections properly carried out In addition refer to figures 2 and 3 to check the fuse and cable dimensions Isolate and secure the source against reclosing Bo...

Page 9: ...ters to select Default settings are as follows Settings Selection Factory default Output Voltage Setting 208 220 230 240 Vac 230V FOR HV series Input Bypass Voltage 10 10 15 15 20 10 15 Input Frequenc...

Page 10: ...RI Output 8 24 VDC Power Fig 5 Caution Max rated values 24Vdc 50mA 15 USB port option Connecting the UPS to your computer is accomplished through the USB port on the back of your computer USB complian...

Page 11: ...Push the ENTER button to confirm and enable your function f If no pressing within 10 seconds it will return to original status 4 ENTER button Use this button to enter enable or confirm the function t...

Page 12: ...CPU Version 19 UPS configurations 1 Various settings that have been chosen are shown in the UPS setting display 2 To enter configuration mode press the FUNC button for one second The first configurati...

Page 13: ...ed For UPS to predict Backup time 0 only internal batteries 1 one external cabinet 2 two external cabinets 0 Site wiring alarm Sit Fault Set You can enable or disable the site wiring alarm Enable Disa...

Page 14: ...ps The UPS is doing a battery test No action needed The UPS will return to normal operation when it successfully completes the battery test Over Charge Constant beep Batteries are overcharged Turn off...

Page 15: ...al and workmanship for a period of 24 months from its original date of purchase 25 10 Technical Specifications GENERAL Rated power 5000VA 6000 VA 8000 VA 10000 VA 12000VA at p f 0 7 Technology On line...

Page 16: ...mber of batteries 20 20 20 20 40 Backup time full load 7 min 6 min 5 min 6 min 6min Recharge time 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 Without ISOTR 280x580x570 280x58...

Page 17: ...28 MAINTENANCE SWITCH NORMAL BY PASS 1 2 INV MAIN INV MAIN or...

Reviews: