POWERCOM 

 

Battery input socket: Connect extra battery case “+” connect with battery positive pole, “-“ connect with battery negative 

pole. 

 

SIMPLE MALFUNCTION SOLUTION 

Use the table below to solve minor UPS installation or operation problems. If any abnormal situation occurs that are not 
listed above, please call service people immediately. 
 

Symptoms 

Possible Cause 

Solutions 

UPS  does  not  give 

any output. 

 

1.

 

Input MCB fault. 

2.

 

Power cord  not connected. 

 

1.

 

 Reset MCB. 

2.

 

Connect Power cord again 

Battery backup fault 

1.

 

Over load 

2.

 

The battery is not fully charged 

3.

 

The battery is bad 

1.

 

Remove some non critical load. 

2.

 

Charge the battery for at least 12 
hours. 

3.

 

Change the battery bank. 

UPS will not turn on 

1.

 

Battery input wire not good. 

2.

 

Battery voltage low. 

3.

 

UPS damaged inside. 

1.

 

Test  battery  and  battery  input 
wire. 

2.

 

Return the UPS for service. 

 

 

 

 
TECHNICAL SPECIFICATIONS 
 

 

Specifications 

AP 1026 

Capacity 

1000VA / 600W 

Voltage 

230V 

Frequency Range 

45-55Hz 

INPUT 

AVR 

145V-275V 

Voltage on Battery 

230V ±5% 

Waveform 

Quasi sinewave 

Power Factor Lagging 

0.6 

OUTPUT 

Sockets 

4 x universal sockets 

Type 

2 x 26 AH external 

BATTERY 

Back up time 

100-120 mins. on 1 PC Load 

Input Protection 

MCB 

O/P short circuit 

UPS shutdown immediately 

PROTECTION 

O/P overload shutdown 

110% for 3 min, 150% for 10 Sec 

TRANSF. TIME  

Mains to Inverter 

4 - 8 ms 

Dimen. (mm) - WxDxH 

145 x 396 x 211 

PHYSICAL 

Weight 

9.00 Kg. 

 

Specification subject to change without prior intimation 
 
 

 
 
 
 
 

 
 
 
 

ASIA POWERCOM P. LTD. 

H.O: 401/402, Arya Arcade, Station Road, Vikhroli (W), Mumbai - 400083.  
Tel:  91-22-61772222 | Fax : 91-22- 25798978 | support@asiapowercom.com  |www.asiapowercom.com 