IMPORTANT SAFETY INSTRUCTION

S

1.

 

WARNING: SAVE THESE INSTRUCTIONS!! 

 

This  Manual  Contains  Important  Instructions  that  should  be  followed  during  Installation  and 

Maintenance of the UPS 

 

WARNING:  Manual  contains  important  instructions  of  UPS  and  batteries  during  installation  and 

maintenance. Follow this instruction at all time 

 

WARNING:

 It is recommended to install UPS in an ANSI/NFPA75 room in which temperature and humidity 

are controlled and free from electrically conductive particles. 

DO NOT 

expose UPS to direct sunlight or 

high heat source; 

DO NOT

 block off ventilation opening around the housing.

 

 

CAUTION:

  Before  conducting  maintenance,  repair,  or  shipment,  please  turn  off  everything  completely 

and disconnect them. 

 

CAUTION: 

The UPS is 

NOT

 applicable for any inductive loads such as motors or domestic appliances like 

hairdryers, speakers, and fluorescent lamps.

 

 

CAUTION:

 All interconnection and power cable should be connected 

ONLY AFTER 

the UPS shut down and 

disconnected from main. 

 

CAUTION:

 Only use No.26 AWG or larger certified cables to connect UPS and device.

 

 

CAUTION:

 

DO NOT

 unplug UPS from main power during operation or protective ground will fail. 

DO NOT

 

disconnect battery under load or shut down may occur.

 

 

CAUTION: 

Ensure the total leakage current of UPS and the connected equipment under 3.5mA. 

 

CAUTION: 

Ensure UPS connects to grounded main power with a fuse or circuit breaker protection.

 

 

CAUTION:

 Dangerous amount of voltage might still exist even the UPS disconnects from the main power 

since residual voltage exists due to battery supply.

 

 

CAUTION:

 Beware of all the details on the cautionary sticker located on UPS.

 

 

CAUTION (No  user-serviceable parts):

 Do  not  attempt to remove  the unit’s  cover, no  user-serviceable 

parts inside. Please refer all service to qualified service technicians.

 

 

CAUTION:

 

DO NOT

 dispose UPS and its batteries to fire, the battery may explode.

 

 

CAUTION:

 

DO NOT

 attempt to open or mutilate the battery.

 

 

User’s operations

: Users only permits to:

 

• Turning the UPS unit on and off. 

• Operating the user interface. 

• Connecting data interface cables. 

• Changing the batteries.

 

 

CAUTION: 

Servicing  of  batteries  should  be  performed  or  supervised  by  personnel  knowledgeable  of 

batteries and the required precautions. Keep unauthorized personnel away from battery

 

 

CAUTION: 

To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch 

circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70.

 

 

CAUTION: 

Maximum ambient temperature 30°C

 

 

CAUTION: 

Intended for Installation in a Controlled Environment.

 

 

DANGER:

 Hazardous electric component inside this unit (example: Heat-sinks) remain energized from the 

battery supply even when the main power is disconnected.

 

 

DANGER:

  Battery  circuit  is  not  isolated  from  the  AC  input.  Hazardous  voltage  may  exist  at  battery 

terminals and ground—test for safety before any direct contact.

 

 

CAUTION: 

Remove the battery’s pole during service inside the battery cabinet or UPS.

 

 

CAUTION:

 

ONLY

 replace batteries with the same type and quantity.

 

WARNING (Fuses)

: Ensure fuse replacement with the same type and rating 

ONLY

.

 

2.

 

Introduction 

 

The information provided in this manual covers Line-Interactive 1025-3000VA

 

uninterruptible power 

system  (UPS). This manual contains  basic functions,  operating procedures, and  emergencies, also  including 

information on how to ship, store, handle, and install the equipment. Only detailed requirements of the UPS 

units  described  herein.  The  installation  must  carry  out  according  to  this  manual.  The  electrical  installation 

must further comply with local legislation and regulations. 

3.

 

Installation 

3.1 Rear panel view 

 
 
 

*Figures only display available function; functions are not on unit if not marked.

 

Summary of Contents for IMD-1025A

Page 1: ...ne Interactive 1025VA 3000VA IMD 1025A IMD 1025AP IMP 1025A IMP 1025AP IMD 1200A IMD 1200AP IMP 1200A IMP 1200AP IMD 1500A IMD 1500AP IMP 1500A IMP 1500AP IMD 2000A IMD 2000AP IMP 2000A IMP 2000AP USE...

Page 2: ...greater distance between the receiver and the equipment Ensure that your Equipment connects to an outlet on a separate circuit Contact a technician experienced with radio and TV or the dealer for tec...

Page 3: ...ceable parts inside Please refer all service to qualified service technicians CAUTION DO NOT dispose UPS and its batteries to fire the battery may explode CAUTION DO NOT attempt to open or mutilate th...

Page 4: ...ne Interactive UPS it is capable of providing clean and stable power to your critical system While the UPS regulates and filters power fluctuation it also keeps the battery charged for any emergency A...

Page 5: ...during Line Battery mode If applicable To avoid electrical hazards please turn off the internal external input breaker Then turn off any external battery breaker and wait till all fans completely shu...

Page 6: ...C to 25 C Protect the equipment from wet or damp areas and moist air To maintain the vitality of the batteries please recharges the UPS at least 8 hours every six months 6 3 Operation CAUTION Ensure t...

Page 7: ...situation feel free to contact for technical assistance PROBLEM POSSIBLE CAUSE Solutions UPS can t operate switching on No lights on no warning sound Power source mistake or low battery power Check th...

Page 8: ...Beep every 2 seconds Low Battery Beep every 0 5 second Environment Operating Humidity 0 90 RH at 0 40 C Non condensing Audible Noise Less than 40 dB IMD Series are same specification with IMP Series...